Overspeed Shutdown: a shutdown will occur when the engine speed reaches this set point.
Factory set to 2400 RPM.
High Level Warning: an alarm will occur if the level reaches this set point. Factory set to 0.0
FT
High Level Shutdown: a shutdown will occur if the level reaches this set point. Factory set to
0.0 FT.
Low Level Warning: an alarm will occur if the level reaches this set point. Factory set to 0.0
FT.
Low Level Shutdown: a shutdown will occur if the level reaches this set point. Factory set to
0.0 FT.
High Flow Warning: an alarm will occur if the flow reaches this set point. Factory set to 0
GPM.
High Flow Shutdown: a shutdown will occur if the flow reaches this set point. Factory set to 0
GPM.
Low Flow Warning: an alarm will occur if the flow reaches this set point. Factory set to 0
GPM.
Low Flow Shutdown: a shutdown will occur if the flow reaches this set point. Factory set to 0
GPM.
High Discharge Pressure Warning: an alarm will occur when the pressure reaches this set
point. Factory set to 0 PSI.
High Discharge Pressure Shutdown: a shutdown will occur when the pressure reaches this
set point. Factory set to 0 PSI.
Low Discharge Pressure Warning: an alarm will occur when the pressure reaches this set
point. Factory set to 0 PSI
Low Discharge Pressure Shutdown: a shutdown will occur when the pressure reaches this
set point. Factory set to 0 PSI
High Suction Pressure Warning: an alarm will occur when the pressure reaches this set point.
Factory set to 0 PSI.
High Suction Pressure Shutdown: a shutdown will occur when the pressure reaches this set
point. Factory set to 0 PSI.
Low Suction Pressure Warning: an alarm will occur when the pressure reaches this set point.
Factory set to 0 PSI
Low Suction Pressure Shutdown: a shutdown will occur when the pressure reaches this set
point. Factory set to 0 PSI