Software Release:
[Application Version 2.8.10128; Configuration Version 2.8.10457]
The Digital Inputs of this menu can be configured from the face of the controller to accept three
types of inputs as the Active state of the input.
High, B(+)
Low, B(-)
Open
The Analog Inputs of this menu can be configured from the face of the controller to accept one of
four types of senders:
Resistive
4-20mA
0-5VDC
Analog.Digital (B- for additional Digital Inputs)
The Outputs are configurable for the operator to choose which output function to use with the
desired output type as shown below.
Relay [10A, Form C]
Digital Out [1A, B(+)]
Digital Out [1A, B(-)]
NOTE: Although the functionality exists to set all analog and digital inputs to the
same function, Enovation Controls strongly advises against this.
Application Configuration
The Application Configuration menu is where an operator will set up the controller's Auto Start
Functions and Auto Throttle Methods, if the intended use is as an auto start and/or auto throttling
controller. Depending on which application is chosen in the menu, there are certain auto start
functions and auto throttling methods hidden that are not pertinent to the application chosen. This
automatic hiding feature allows for a simpler, more intuitive controller menu in the MPC-10 / TEC-10.
Review Application Configuration under the Menu Glossary section of this manual for the full list and
definition of each setting.
NOTE: Discharge Pressure is the only pressure type available for Auto
Start/Stop and/or Auto Throttle control by pressure.
Pump All Purpose
The Pump All Purpose application houses auto start functions and auto throttling methods of
the controller for common pumps used in rental applications.
The auto start functions and auto throttle methods are:
Auto Start/Stop Functions
Single Contact
Local Start (Green Start key)
Two Contact Maintained (Dual Floats)
Auto Throttle Methods
Running Loaded RPM
Pressure Transducer (will require an analog input setting)
Section 40
2016-04-19
13
00-02-0939