Fike SHP 10-051 Product Manual

Fike SHP 10-051 Product Manual

Conventional fire alarm/suppression system

Advertisement

Product Manual
P/N: 10-051
Conventional
Fire Alarm/Suppression
System
Manual P/N: 06-130
Rev. No: 3, 04/02
firealarmresources.com

Advertisement

Table of Contents
loading

Summary of Contents for Fike SHP 10-051

  • Page 1 Product Manual P/N: 10-051 Conventional Fire Alarm/Suppression System Manual P/N: 06-130 Rev. No: 3, 04/02 firealarmresources.com...
  • Page 2 firealarmresources.com...
  • Page 3 Fike authorized sales outlets, who have been trained in an approved manner by Fike, and the user who is a customer of the Fike authorized sales outlet. Fike does not warrant that this manual is technically correct, complete, or free from writing problems or that the Fike products referenced therein are free from minor flaws.
  • Page 4 firealarmresources.com...
  • Page 5: Table Of Contents

    FIKE CORPORATION TABLE OF CONTENTS Section Page 1.0 Preface..............................1 About This Manual ......................1 Product Support ........................1 Revision History ........................1 Terms Used in this Manual ....................1-3 Symbols Used in this Manual....................4 Safety Notices ........................4 2.0 Product Overview ..........................
  • Page 6 FIKE CORPORATION 6.0 Servicing .............................. 33 Checkout ........................... 33 Maintenance........................33 Troubleshooting ......................33-36 Appendix 1 ..............................37 Battery Calculations ........................37-38 Appendix 2 ..............................39 ULC Operation ..........................39 Appendix 3 ..............................41 System Operation Posting ......................41 Index ................................43...
  • Page 7: Section Page

    Single Hazard Panel (SHP) Fire Alarm/Suppression Control System. The information contained in this manual must be utilized by the factory trained Fike sales outlet in order to properly install, test and service the SHP. This manual can also be used by the end user as an Operations Manual for the SHP.
  • Page 8 PREFACE FIKE CORPORATION Class A wiring Input circuits capable of transmitting an alarm signal during a single open or a non-simultaneous single ground fault on a circuit conductor shall be designated as Style D or Class A. Similarly, output circuits capable of activating during a single open or a non-simultaneous ground fault on a circuit conductor shall be designated as Style Z or Class A.
  • Page 9 FIKE CORPORATION PREFACE Sequential Detection A detection scheme where the sum total of active detectors on the initiating circuits must be two or more before the system will enter the pre-discharge state. Single Detector Release A detection scheme where activation of one detector causes the system to Detection enter the pre-discharge state.
  • Page 10: Symbols Used In This Manual

    Always ground yourself with a proper wrist strap before handling the module(s). If the installer is grounded at all times, damage due to static discharge will not occur. If the module requires repair or return to Fike, it must be shipped in an anti-static bag.
  • Page 11: Product Overview

    PRODUCT DESCRIPTION The Fike SHP (P/N 10-051) is a compact, cost-effective, conventional fire alarm and suppression releasing panel. The SHP is designed for use with Fike Clean Agent Fire Suppressant, CO , or sprinkler (pre-action/deluge) suppression systems. The SHP controller is shipped from the factory pre-configured for Clean Agent suppression operation.
  • Page 12: Related Documentation

    OVERVIEW FIKE CORPORATION The installer should also be familiar with the following documents and standards: National Fire Protection Association (NFPA) Codes: NFPA 12 – Carbon Dioxide Extinguishing Systems (High Pressure Only) NFPA 12A – Halon 1301 Extinguishing Systems NFPA 13 – Sprinkler Systems NFPA 15 –...
  • Page 13: Shp Features

    FIKE CORPORATION OVERVIEW SHP FEATURES • • General Initiating Device Circuits Microprocessor-controlled Up to two Style B initiating device circuits capable of sequential alarm, Power-limited on all circuits except cross-zone, or single detector release power connections (P1) operation with an overall system...
  • Page 14 OVERVIEW FIKE CORPORATION This page intentionally left blank Page 8 of 43 SHP Product Manual UL S2203 Rev. No. 3, 04/02 Manual P/N: 06-130 FM 0Z8A0.AY firealarmresources.com...
  • Page 15: Equipment/Products

    Includes the main controller with transformer and AC terminal block inside steel enclosure (red or gray). The enclosure door is equipped with a standard Fike keylock and a viewing window covered with clear lexan. The enclosure includes space for installing batteries (up to 18 AH – ordered separately).
  • Page 16 EQUIPMENT FIKE CORPORATION • 10-2172 CLASS A INPUT MODULE The optional Class A Input Module allows any of the four initiating device circuits to be wired Class A (Style D) versus the standard Class B (Style B) method. The Class A module mounts directly onto the SHP Controller utilizing four stand-offs supplied with the module.
  • Page 17: Input Devices

    SHP. Refer to the Detection Input Compatibility portion of Section 3.6, Specifications, for selecting the appropriate detector base and head. Other devices such as contact closure input devices, contact closure detectors, notification appliances, and Solenoids are all listed in the Fike Compatibility Document, P/N 06-186. Old Part Number Part Number...
  • Page 18: Output Devices

    63-1012 Relay Base This 6” base is equipped with a 430Ω resistor and two sets of Form “C” relay contacts. OUTPUT DEVICE Refer to FIKE Notification Appliance and Releasing Compatibility Document (06-186). Page 12 of 43 SHP Product Manual UL S2203 Rev.
  • Page 19: Ancillary Devices

    Agent Suppressant Container. Refer to the ARM manual, 06-106 for detailed instructions on the ARM. • 10-107 – 10-110 Conventional Graphic Annunciator Fike Graphic Annunciators provide a graphic display of the protected area using LED’s to indicate the location of smoke detectors. UL S2203...
  • Page 20: Spare Parts

    02-3774 Power terminal (P1) yellow cover 02-4007 Flashbulb (for testing ARM III release) 12/box 02-3799 Touch-Up Paint (Not available from Fike) Red-Sherwin Williams - #F63VXR9951-4343 Polane 2.8T Plus Polyurethane Enamel Gray-Sherwin Williams - #F63VXA9975 Polane T Plus Polyurethane Enamel Page 14 of 43...
  • Page 21: Specifications

    FIKE CORPORATION EQUIPMENT SPECIFICATIONS Environmental: All electronics are rated 32° - 120°F (0° - 49°C) 85% relative humidity Primary Input AC Power: 120 VAC, 50/60 Hertz, 1.42 Amps, 170 VA 208/240VAC, 50/60 Hertz, 0.82 Amps @ 208VAC, 0.71 Amps @ 240VAC, 170 VA System AC line power must originate from a dedicated circuit at the main building power distribution center.
  • Page 22 EQUIPMENT FIKE CORPORATION DETECTION BASE COMPATIBILITY Maximum Bases per Circuit Single Fike P/N Size Char. Manufacturer Mfg. P/N Sequential Cross Detector Zone Release Ω Ω Ω Ω 67-1034 6” Hochiki NS6-224 None 67-1036 4” Hochiki NS4-224 None C02-1164 6” Hochiki...
  • Page 23 2.7 K EOL 15-16 Suppressant 24 VDC nominal Agent Agent Release Power limited Requires Fike’s ARM III, P/N 10-1832 Release output Class B (Style Y) 6 ARM III’s maximum Module Maximum wire resistance: 35 Ω Fike tested and UL/FM approved valves,...
  • Page 24 EQUIPMENT FIKE CORPORATION • P4 – Relays: TERMINAL DESCRIPTION WIRING SPECIFICATION DETAILS 27 C Common SPDT Form C relay contact 28 NC Alarm Power limited DC operation: 5 amps @30VDC (pf=.35) Normally Closed AC operation: 5 amps @250VAC (pf=.35) 29 NO...
  • Page 25: Enclosure Specifications

    FIKE CORPORATION EQUIPMENT ENCLOSURE SPECIFICATIONS • Mounting Methods: Surface: Use tear-drop openings in back of back-box Flush: Use tear-drop openings in back of back-box and 3/16 dia. thru holes, 2 each side for secure installation. This method provides a ½ “ lip around back-box and removable door with full swing.
  • Page 26 EQUIPMENT FIKE CORPORATION This page intentionally left blank Page 20 of 43 SHP Product Manual UL S2203 Rev. No: 3, 04/02 Manual P/N: 06-130 FM 0Z8A0.AY firealarmresources.com...
  • Page 27: Installation

    If the installer is grounded at all times, damage due to static discharge will not occur. If the module requires repair or return to Fike, it must be shipped in an anti-static bag.
  • Page 28: Power And Field Wiring

    INSTALLATION FIKE CORPORATION POWER AND FIELD WIRING Field Wiring / Power Limited Requirements: Route all field wiring through the appropriate conduit knockouts. Provide adequate wire length for strain relief. SHP terminal blocks (including SRM4 and Class-A modules) accept single wire from 14 to 30 AWG.
  • Page 29: Wiring Verification

    FIKE CORPORATION INSTALLATION WIRING VERIFICATION After pulling the wire into the enclosure, verify wire for ground-fault absence and acceptable impedances prior to connecting the initiating and indicating circuits. CAUTION: Field devices shall not be connected if using meggar or any means that applies voltages in excess of device ratings (to prevent damage to the devices).
  • Page 30: Wiring Diagrams

    INSTALLATION FIKE CORPORATION WIRING DIAGRAMS SHP CONTROLLER 2.7 K EOL SOLENOID C85-102 ARM III ARM III 6 ARM III MAXIMUM (OR) TWO 12V SOLENOIDS COMMON FOR Aux V OUT (OR) TOTAL OF 0.5 Amps Aux +24 V OUT RESETTABLE Aux+24V OUT...
  • Page 31 FIKE CORPORATION INSTALLATION SRM4, 10-2176 RELAY MODULE In Sprinkler mode, SRM4 Relay4 (trouble) has reversed labels since relay is normally energized. R E LA Y 3 RELA Y 6 RELA Y 5 RELA Y 4 RELA Y 3 NO NC C...
  • Page 32: Circuit Configuration

    Abort contact monitoring input. Abort definitions are at the end of this section. ARM: Release circuit to fire GCA via Agent Release Modules (Fike P/N 10-1832). Solenoid: Solenoid release circuit used with either two 12V Fike CO2 solenoids or listed industry 24VDC solenoids. Page 26 of 43 SHP Product Manual UL S2203 Rev.
  • Page 33 FIKE CORPORATION INSTALLATION SW3 CONFIGURATION The operation characteristics of the SHP system is determined by the configuration dip switches located on the SHP Controller (SW3). These switches allow you to field define the operation of the SHP. NOTE: Bold values indicate default positions (0001 1000 01) in S1 to S10 order. 0=off. Default position only has switch positions S4, S5, &...
  • Page 34: Initial Power-Up

    INSTALLATION FIKE CORPORATION INITIAL POWER-UP Prior to power-up, interconnect the transformer secondary winding to SHP P1-1 & P1-2 per the wiring diagram. Ensure AC power is wired per the wiring diagram at the end of this section. If using a solenoid (rather than the ARM-III), remove the EOL from the AgtRel circuit. If configured for solenoid operation, but a solenoid is not used (such as alarm system), the solenoid can be simulated with a 30 Ω, high (>20) Wattage or 200 Ω, 5W resistor on terminals 17 to 18.
  • Page 35: Operations

    FIKE CORPORATION OPERATIONS OPERATIONS USER SWITCH INTERACTION POWER LIMITED RELEASE CIRCUITS The user switches provide these capabilities: AUDIBLE #1 AUDIBLE #2 AUDIBLE #3 AGENT RELEASE SOLENOID MODULE Silence Switch: Silences audibles (if currently sounding) & piezo. Changes flashing LED’s to steady. Also used to resound silenced outputs per below.
  • Page 36: Outputs Disabled Mode

    OPERATIONS FIKE CORPORATION OUTPUTS DISABLED MODE Holding silence switch active, then momentarily pressing reset switch puts system into the “Outputs Disabled Mode”. A system in the “Outputs Disabled Mode” has: * Output circuits 1-5 disabled from activation * Alarms Silenced LED is ON.
  • Page 37: Alarm Operation (Suppression Mode)

    FIKE CORPORATION OPERATIONS 5.10 ALARM OPERATION (IN SUPPRESSION MODE) Upon alarm of a first detector, system enters alarm state. Typical response includes: Piezo: Chirp (On & Off pattern) until silenced. Alarm LED: Flash. After silencing, illuminate steady. Alarm Relay: Activate.
  • Page 38: Alarm Operation (Sprinkler Mode)

    OPERATIONS FIKE CORPORATION 5.11 ALARM OPERATION (IN SPRINKLER MODE) Operation is same as in the Suppression mode, except: Alarm audibles and pre-discharge audibles remain on during subsequent states. Abort operation is not available. Upon waterflow input activation, system enters release state. Typical response changes to: Piezo: Chirp (On &...
  • Page 39: Servicing

    Periodic maintenance shall be, as a minimum, performed per NFPA 72, Chapter 7. Maintenance shall be performed by a trained or authorized Fike representative. Certain components of the SHP require replacement, even though no obvious sign of failure is present.
  • Page 40 SERVICING FIKE CORPORATION 6.3.1 Typical Voltages and Tolerances V= DC volts All voltages reference to SHP power ground @ T1 26.3 VAC 25.4 VAC no load 6.5 VAC prim Restore 100.2VAC prim 1 – 2 24 VAC no load full load brown out 20.9VAC sec...
  • Page 41 FIKE CORPORATION SERVICING 6.3.2 EVENT DESCRIPTION / POSSIBLE RESOLUTION Diagnostic Display Code Description Tips to Resolve Input Circuit 1 open ♦ Verify correct value EOL Resistor (4.3 K - Yellow-Orange-Red) has been installed. Input Circuit 2 open ♦ Measure field wiring resistance = 20 Ω or less.
  • Page 42 SERVICING FIKE CORPORATION Ground Fault ♦ Verify standoff in the center of the SHP Control Board does not have the retaining nut installed ♦ Remove field wiring from terminal strips to isolate the wire with the ground fault. When panel clears troubleshoot wire.
  • Page 43: Battery Calculations

    FIKE CORPORATION APPENDIX 1 APPENDIX 1 BATTERY CALCULATIONS The SHP is designed for use with either of two battery packs. Each battery pack contains two 12V batteries which can be installed in the SHP enclosure. Battery back-up duration must be extended for sprinkler supervisory systems.
  • Page 44 APPENDIX 1 FIKE CORPORATION SHP Battery Calculation Form Back-up Hours required: (24, 60 or 90 hours) Normal Operation: Controller Current 0.090 A Auxiliary Output Current: _____ A Total Normal Current = _____ X ____hours = ____A-H Alarm Operation: Controller Current 0.090 A...
  • Page 45: Ulc Operation

    The SHP control system requires additional operating characteristics in order to be compliant with ULC527. In order to meet this criteria, additional control panel configurations are available PART NUMBERS The following part numbers shall be used to order the ULC version of the SHP control system. Fike Part Number Description 10-2171-CN SHP Controller...
  • Page 46 APPENDIX 3 FIKE CORPORATION “System Operation Posting” on the next page is offered without headers or footers so that the sales outlet may make copies to post adjacent to control equipment. Page 40 of 43 SHP Product Manual UL S2203 Rev.
  • Page 47: System Operation Posting

    IN CASE OF TROUBLE CONTACT: __________________________________________________ __________________________________________________ __________________________________________________ Phone # ___________________________________________ Customer Service Department Fike Protection Systems Division of Fike Corporation (816) 229 - 3405 Refer to Fike Installation, Operation and Maintenance Manual #06-130 Frame this sheet and place adjacent to control equipment. firealarmresources.com...
  • Page 48 firealarmresources.com...
  • Page 49: Index

    FIKE CORPORATION INDEX INDEX Power Calculations .......... 38 Power Limited ..........22 Pre-discharge ......2, 26, 27, 31, 32 0 ohm jumper ..........23,24 Relays ............. 31 Abort....1, 15, 22, 25, 26, 29, 31, 32, 36 Release…….1, 2, 3, 6, 7, 12, 13, 15, 16, 17, 25, Alarm……1, 2, 5, 6, 7, 13, 18, 21, 26, 27, 29, 30,...
  • Page 50 firealarmresources.com...
  • Page 51 firealarmresources.com...
  • Page 52 704 South 10 Street P.O. Box 610 Blue Springs, Missouri 64013 U.S.A. (816) 229-3405 Fax: (816) 229-0314 http://www.fike.com firealarmresources.com...