P3 – Output Circuits:
NOTE: Total current for system modules, notification appliances circuits, and regulated power
circuits MUST not exceed the 2.6 Amps supplied by the SHP controller (unless also using the
auxiliary input power).
TERMINAL
DESCRIPTION
6, 8
Resettable Auxiliary
RES
Output Power
Auxiliary
Output
7-8
Auxiliary Output
Auxiliary
Power
Output
NOTE: Resettable and non-resettable auxiliary power output share the same negative (common
ground) output (terminal 8).
TERMINAL
DESCRIPTION
9-10
AUDIBLE #1
11-12
AUDIBLE #2
Notification
outputs
13-14
AUDIBLE #3
15-16
Suppressant
Agent
Agent Release
Release
output
Module
Sprinkler and CO
Solenoid Release
17-18
output
Solenoid
FIELD WIRING LIMITATIONS FOR AUDIBLE AND SOLENOID OUTPUTS
Max Current (Amps)
Audibles 1-3 (Max Ωs)
Agent Release (Max Ωs)
Solenoid (Max Ωs)
UL S2203
FM 0Z8A0.AY
WIRING
24VDC nominal
Power limited
24 VDC nominal
Power limited
WIRING
24VDC nominal
Power limited
Class B (Style Y)
Maximum wire
resistance limited
by the chart below
24 VDC nominal
Power limited
Class B (Style Y)
24 VDC nominal
2
Power limited
Class B (Style Y)
0.1
0.2
0.3
0.4
0.5
24
12
8
6
4.8
35
35
35
35
35
12
6
4
3
2.4
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
SPECIFICATION DETAILS
Used for 4-wire type detectors or others
requiring power to drop out temporarily
upon reset of the control panel.
500mAmp maximum
Used for graphic annunciator or other
devices requiring constant 24VDC.
500mAmp maximum
SPECIFICATION DETAILS
2.0 K End-of-line resistor (EOL)
2 Amps maximum
Listed for use with any 18-30VDC polarity
reversal indicating appliance listed for fire
alarm signaling
Fike tested indicating appliances
compatible with the SHP are detailed in the
Fike compatibility document, P/N 08-186
2.7 K EOL
Requires Fike's ARM III, P/N 10-1832
6 ARM III's maximum
Maximum wire resistance: 35 Ω
Fike tested and UL/FM approved valves,
0.100 – 2 amp valve (12-240 Ω) detailed in
the Fike compatibility document. P/N 06-
186 (FM Group 2 panel)
The solenoid circuit does not require an
EOL, it supervises through the coil for
wiring integrity. To simulate the proper
solenoid resistance, a 200 Ω – 5 watt
resistor can be used (P/N 02-2686)
0.6
0.8
1.0
1.5
4.0
3.0
2.4
1.6
35
35
35
35
2.0
1.5
1.2
0.8
EQUIPMENT
2.0
1.2
35
0.6
Page 17 of 43
Rev. No: 3, 04/02