Fike SHP 10-051 Product Manual page 42

Conventional fire alarm/suppression system
Table of Contents

Advertisement

SERVICING
0
A
b
NOTE: The letter "b" is often
confused with the # 6
C
C.
d
E
E.
F
F.
-
-.
Page 36 of 43
Rev. No: 3, 04/02
Ground Fault
Valid Abort
Missing battery
nd
2
Alarm active on input 1 if
using 430Ω bases. Always
activates on first alarm if using
220Ω or 0Ω devices.
nd
2
Alarm active on input 2 if
using 430Ω bases. Always
activates on first alarm if using
220Ω or 0Ω devices.
Low Voltage (<19 volts)
Intelli-Fet lost
5V Reference/A-D Failure
Abort, premature
Abort, Late
AC Brown – out (<85%)
Auxiliary Power Input (<15V) ♦
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
FIKE CORPORATION
Verify standoff in the center of the SHP Control
Board does not have the retaining nut installed
Remove field wiring from terminal strips to
isolate the wire with the ground fault. When
panel clears troubleshoot wire.
Normal Operation Information
Verify batteries are installed properly.
Verify each battery has approximately the same
voltage.
Remove battery wiring harness and replace with
a 100uF 50 watt capacitor and verify charger
voltage (Reference Section 6.3.1)
Input circuit 1
Input Circuit 2
Reference Section 5.9, Low Power Conditions
Check AC and DC power input.
Reset panel, if trouble does not clear replace
SHP Control Board.
Reset panel, if trouble does not clear replace
SHP Control Board.
Normal Operation Information
Normal Operation Information
Reference Section 6.3.1, Typical Voltages and
Tolerances
Check auxiliary power supply voltage (P1 Aux.
Input).
UL S2203