SERVICING
0
A
b
NOTE: The letter "b" is often
confused with the # 6
C
C.
d
E
E.
F
F.
-
-.
Page 36 of 43
Rev. No: 3, 04/02
Ground Fault
Valid Abort
Missing battery
nd
2
Alarm active on input 1 if
using 430Ω bases. Always
activates on first alarm if using
220Ω or 0Ω devices.
nd
2
Alarm active on input 2 if
using 430Ω bases. Always
activates on first alarm if using
220Ω or 0Ω devices.
Low Voltage (<19 volts)
Intelli-Fet lost
5V Reference/A-D Failure
Abort, premature
Abort, Late
AC Brown – out (<85%)
Auxiliary Power Input (<15V) ♦
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
FIKE CORPORATION
♦
Verify standoff in the center of the SHP Control
Board does not have the retaining nut installed
♦
Remove field wiring from terminal strips to
isolate the wire with the ground fault. When
panel clears troubleshoot wire.
♦
Normal Operation Information
♦
Verify batteries are installed properly.
♦
Verify each battery has approximately the same
voltage.
♦
Remove battery wiring harness and replace with
a 100uF 50 watt capacitor and verify charger
voltage (Reference Section 6.3.1)
♦
Input circuit 1
♦
Input Circuit 2
♦
Reference Section 5.9, Low Power Conditions
♦
Check AC and DC power input.
♦
Reset panel, if trouble does not clear replace
SHP Control Board.
♦
♦
Reset panel, if trouble does not clear replace
SHP Control Board.
♦
Normal Operation Information
♦
Normal Operation Information
♦
Reference Section 6.3.1, Typical Voltages and
Tolerances
Check auxiliary power supply voltage (P1 Aux.
Input).
UL S2203
FM 0Z8A0.AY