APPENDIX 1
Normal Operation:
Controller Current
Auxiliary Output Current:
Alarm Operation:
Controller Current
SRM4 Current (0.100 if using SRM4, else 0.0)
Output Device Current:
Auxiliary Output Current:
Power Supplied:
Controller Supplied Current:
Auxiliary In current:
Total Current Supplied =
Total Battery Pack A-H available (7 or 18 A-H):
Normal Operation:
Controller Current
Auxiliary Output Current:
Alarm Operation:
Controller Current
SRM4 Current (0.100 if using SRM4, else 0.0)
Output Device Current:
Auxiliary Output Current:
Power Supplied:
Controller Supplied Current:
Auxiliary In current:
Total Current Supplied =
Total Battery Pack A-H available (7 or 18 A-H):
Page 38 of 43
Rev. No: 3, 04/02
SHP Battery Calculation Form
Back-up Hours required: (24, 60 or 90 hours)
Total Normal Current =
Total Alarm Current = _____ X
Must exceed
SHP Battery Calculation Form
Example
Back-up Hours required: (24 or 90 hours)
Total Normal Current =
Total Alarm Current = 1.29 X
Must exceed
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
FIKE CORPORATION
0.090 A
_____ A
_____ X
____hours = ____A-H
0.090 A
_____ A
_____ A
_____ A
0.166 hours = ____A-H
Total A-H used =
(X1.2 factor)
Total Power Required
2.6 Amps
______ Amps
Must exceed
______ Amps
0.090 A
0.10 A
0.19 X
24 hours =
0.090 A
0.10 A
1.00 A
0.10 A
0.083 hours = 0.11 A-H
Total A-H used =
(X1.2 factor)
Total Power Required
2.60 Amps
0.00 Amps
Must exceed
2.60 Amps
____A-H
____A-H
____A-H
4.6 A-H
4.71 A-H
5.65 A-H
7.0 A-H
UL S2203
FM 0Z8A0.AY