Section Page; Preface; About This Manual; Product Support - Fike SHP 10-051 Product Manual

Conventional fire alarm/suppression system
Table of Contents

Advertisement

FIKE CORPORATION
1.0

PREFACE

1.1

ABOUT THIS MANUAL

This manual is intended to be a complete reference for the installation, operation, and service of the Fike
Single Hazard Panel (SHP) Fire Alarm/Suppression Control System. The information contained in this
manual must be utilized by the factory trained Fike sales outlet in order to properly install, test and service
the SHP. This manual can also be used by the end user as an Operations Manual for the SHP.
Before you refer to any section in this manual, and before you attempt to install or use the SHP, be sure
to read the important safety notices in section 1.6.
This manual is divided into sections for easy reference. The first-time installer and/or user should
thoroughly read and understand the instructions contained within this manual before using this device.
These instructions must be followed to avoid possible damage to the SHP itself or adverse operating
conditions caused by improper installation and programming.
1.2

PRODUCT SUPPORT

If you have a question or encounter a problem not covered in this manual, you should first try to contact
the sales outlet that installed the protection system. Fike has a worldwide distribution network. Each
sales outlet sells, installs, and services Fike equipment. Look on the inside door, left side, there should
be a sticker with an indication of the sales outlet who sold the system. If you can not locate the sales
outlet, please call Fike Customer Service for locating your nearest sales outlet, or go to our web-site at
www.fike.com. If you are unable to contact your installing sales outlet or you simply do not know who
installed the system you can contact Fike Product Support at (816) 229-3405, Monday through Friday,
8:00 a.m. to 5:00 p.m. CST.
1.3

REVISION HISTORY

Document Title: SHP Conventional Fire Alarm/Suppression System Product Manual
Document Reorder Number: 06-130
Revision
0
1
2
3
Section 4.6, 6.3.1
1.4

TERMS USED IN THIS MANUAL

The following are various terms used in this manual with a brief description of each:
Term
Ω Ω Ω Ω
AC Normal State
Abort
Alarm State
UL S2203
FM 0Z8A0.AY
Section
All Sections
All Sections
All Sections
Description
Symbol for "ohm". Unit of resistance.
("AC Normal" Green LED ON) The system is in the AC Normal state when
appropriate AC power is being applied to the system.
An input to a suppression system to prevent an unwanted discharge of fire
suppressant agent. The SHP has several different abort types.
("Alarm" Red LED ON, Piezo pulsing) The alarm occurs when an input circuit
configured for alarm operation has been activated. Activation typically
initiated by a detector or contact device. The system leaves the alarm state
upon entry into the pre-discharge or release state.
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
Date
Reason for Change
06/12/96
Initial Release
11/02/99
ULC Additions
12/01/01
Product Update
04/02
Added wiring and correct
PREFACE
Page 1 of 43
Rev. No. 3, 04/02

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents