Shp Features - Fike SHP 10-051 Product Manual

Conventional fire alarm/suppression system
Table of Contents

Advertisement

FIKE CORPORATION
2.5

SHP FEATURES

General
Microprocessor-controlled
Power-limited on all circuits except
power connections (P1)
Field selection of either sprinkler
(solenoid) or suppression (ARM-III)
operation
Eight system status LEDs to provide
positive indication of system status
Seven segment diagnostic LED for
trouble and event occurrences
System configuration via dip-switches
Local piezo with distinct event tones
Reset switch
Audible silence switch
Disable Mode for audible and release
circuits
Disable switch for release circuits
Alarm and trouble resound
Power
Integral 2.6 amp power supply at
24VDC nominal
Selection of 120, or 240/208 VAC power
input at 50 or 60 hertz
Supplemental power input capability up
to 8 amps at 24 VDC
Resettable and non-resettable regulated
power output
Battery/Earth fault supervision
7 AH to 18 AH battery options, up to 90
hours standby
Enclosure
Steel enclosure 21" high by 14.35" wide
by 4" deep (Back-box dimensions)
Enclosure is equipped with a .50" wide
lip to facilitate flush mounting
Removable door for easy installation
Enclosure is available in Red or Gray
UL S2203
FM 0Z8A0.AY
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
Initiating Device Circuits
Up to two Style B initiating device
circuits capable of sequential alarm,
cross-zone, or single detector release
operation with an overall system
capacity of 50 detectors maximum
Up to three Style B initiating device
circuits capable of monitoring closed
contact devices
Optional Class A module that converts
all four initiating device circuits to Style
D wiring and operation
Notification Appliance Circuits
Three Style Y notification appliance
circuits rated at 2.0 amps each
Releasing Circuits
One Agent Release circuit with
maximum of 6 ARM III's
or
One Solenoid release circuit which can
activate one 24V or two 12V solenoids
Relays
General Alarm and Trouble relays
Optional SRM4 module to add four
DPDT dry relay contact outputs
Sprinkler Monitoring Points
Waterflow input
Supervisory input
OVERVIEW
Page 7 of 43
Rev. No: 3, 04/02