Alarm Operation (Sprinkler Mode); Supervisory Operation - Fike SHP 10-051 Product Manual

Conventional fire alarm/suppression system
Table of Contents

Advertisement

OPERATIONS
5.11
ALARM OPERATION (IN SPRINKLER MODE)
Operation is same as in the Suppression mode, except:
Alarm audibles and pre-discharge audibles remain on during subsequent states.
Abort operation is not available.
Upon waterflow input activation, system enters release state. Typical response changes to:
Piezo:
Release LED:
Alarm, Waterflow Relays:
Alarm, Pre-discharge, Waterflow Audibles:
Solenoid Circuit:
Waterflow outputs are latching as they remain on after deactivation of waterflow input.
Manual Release activation does not activate waterflow output.
Manual Release operation does activate both the alarm and pre-discharge audibles.
NOTE: During activation of multiple events, piezo priority is alarm over supervisory over trouble.
5.12

SUPERVISORY OPERATION

Upon activation of a supervisory input, system enters supervisory state. Typical response includes:
Piezo:
Supervisory LED:
Supervisory Relay:
Supervisory Audibles:
Upon deactivation of the supervisory input, typical system response includes:
Piezo:
Supervisory LED:
Supervisory Relay:
Supervisory Audibles:
Diagnostic LED:
5.13
TROUBLE OPERATION
Upon occurrence of a trouble condition, system enters trouble state. Typical response includes:
Piezo:
Trouble LED:
Trouble Relay:
Diagnostic LED:
Upon Trouble clear (except for latching troubles), system performs a trouble-clear-reset. Typical
response includes:
Piezo:
Trouble LED:
Trouble Relay:
Diagnostic LED:
Page 32 of 43
Rev. No: 3, 04/02
Chirp (On & Off pattern) until silenced.
Flash. After silencing, illuminate steady.
Activate.
Activate until silenced.
Activate.
Warble (On & Off pattern) until silenced.
Flash. After silencing, illuminate steady.
Activate.
Activate until silenced.
Off
Flash every 10 seconds until manual reset.
Off.
Off.
Displays code corresponding to supervisory input.
Steady on until silenced.
Flash. After silencing, illuminate steady.
Activate.
Displays code or codes corresponding to trouble conditions.
Off
Blink every 10 seconds until manual reset.
Off.
Displays code or codes corresponding to trouble conditions.
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
FIKE CORPORATION
UL S2203
FM 0Z8A0.AY

Hide quick links: