Circuit Configuration - Fike SHP 10-051 Product Manual

Conventional fire alarm/suppression system
Table of Contents

Advertisement

INSTALLATION
4.7

CIRCUIT CONFIGURATION

These columns define four basic operation modes selected by SW3. Position S1 (suppression versus
sprinkler) and S2 (sequential versus cross-zone detection). Switch position S7 and S8 allow further
customization.
NOTE: The Agent Release Module circuit and the Solenoids circuit can't be used concurrently.
S1:
Suppression Mode (S1 = Off)
S2:
Sequential (Off)
In #1 *
Sequential Det.
In #2 *
Seq. Det./ Supervisory
In #3
Manual Release
In #4
Abort In
Aud #1
Alarm
Aud #2
Pre-discharge
Aud #3
Release
Agt Rel
ARM (S7 = Off)
Sol
Solenoid (S7 = On)
Rel #1
Alarm
Rel #2
Trouble
Rel #3
Alarm
Rel #4
Pre-discharge
Rel #5
Release
Rel #6
Abort/Superv
Italicized Supervisory/Manual Release options are activated when switch S8 = On
* Clip the pertinent 0 ohm jumper if using 0 ohm bases or contact closure devices.
Relays are dry contact outputs which activate up on the given states listed above.
Relays 1-2 are on SHP controller. Relays 3-6 are on optional SRM4 relay module.
Alarm, Pre-discharge, Release, and Waterflow relays are latching (do not clear until reset).
Abort, Supervisory, and trouble relays reflect current system status (except for latching troubles).
Sequential Det:
Sequential Zone detection circuit as described in Section 1.4.
Cross-Zone Det:
Cross-Zone detection circuit as described in Section 1.4.
Superv(isory):
Supervisory contact monitoring input circuit or indicating circuit.
Manual Rel:
Manual Release contact monitoring input circuit. Overrides aborts.
Waterflow:
Waterflow contact monitoring input circuit. Activates:
Abort In:
Abort contact monitoring input. Abort definitions are at the end of this section.
ARM:
Release circuit to fire GCA via Agent Release Modules (Fike P/N 10-1832).
Solenoid:
Solenoid release circuit used with either two 12V Fike CO2 solenoids or listed
industry 24VDC solenoids.
Page 26 of 43
Rev. No: 3, 04/02
Sprinkler Mode (S1 = On)
Cross-Zone (On)
Sequential (Off)
Cross-Zone Det.
Sequential Det.
Cross-Zone Det.
Seq. Det. /
ManRel
Manual Release
Waterflow
Abort In
Supervisory
Alarm
Alarm
Pre-discharge
Predis / Superv
Release
Waterflow
ARM (S7 = Off)
Disabled
Solenoid (S7 = On)
Solenoid
Alarm
Alarm
Trouble
Trouble
Alarm
Alarm
Pre-discharge
Trouble
Release
Waterflow
Abort
Supervisory
a.) solenoid output
b.) Audibles: Waterflow, alarm, and pre-discharge
c.) Relays: Waterflow and alarm
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
FIKE CORPORATION
Silenceable
Cross-Zone (On)
Cross-Zone Det.
Cross-Zone Det.
Waterflow
Supervisory
Alarm
Silenceable
Predis / Superv
Silenceable
Waterflow
Silenceable
Disabled
Non
Solenoid
Non
Alarm
Non
Trouble
Non
Alarm
Non
Trouble
Non
Waterflow
Non
Supervisory
Non
UL S2203
FM 0Z8A0.AY