FIKE CORPORATION
5.0

OPERATIONS

5.1

USER SWITCH INTERACTION

The user switches provide these capabilities:
Silence Switch: Silences audibles (if currently sounding) & piezo.
Changes flashing LED's to steady. Also used to
resound silenced outputs per below.
Reset Switch:
Resets system including turning off outputs,
interrupting resettable power. Momentarily
activates piezo, all LED's, and trouble relay.
Restores system to normal state.
SW4:
Arms or Disables the release circuits (Agent
Release and Solenoid).
5.2

DIAGNOSTIC LED CODE DESIGNATORS

The seven segment diagnostic LED cycles through display of these codes (with or with-out a period) for
the events that have occurred since the last reset. For example, if input circuit #3 is activated, the LED
displays "3.".
NOTE: The period portion of the display is often overlooked. When viewing the diagnostic codes,
do not overlook the period.
Circuit/Mode
Input # 1
Input # 2
Input # 3
Input # 4
Audible # 1
Audible # 2
Audible # 3
Agent Release
Module
Solenoid
System
Abort Input
Battery Failure
nd
2
Alarm Active
System Voltage
Microcontroller
Invalid Abort
Power Failure
5.3

SILENCING RULES

The Silence switch silences all activated audibles (but does not effect Relays).
Silenced audibles are resounded by pressing silence switch (while all audibles are silenced).
When manually unsilencing, local piezo is not re-annunciated
After silencing, entry into new states only sounds that state's audibles (except entry into release state
resounds pre-discharge audibles plus also resounds alarm audibles in sprinkler mode).
Alarm, waterflow, supervisory, pre-discharge, release and trouble LED's stay on steady after silencing
to acknowledge operator action (except upon event clear per Section 5.5).
UL S2203
FM 0Z8A0.AY
Code
Status
without
period
1
Open
2
Open
3
Open
4
Open
5
Open
6
Open
7
Open
8
Open
9
Open
0
Ground Fault
A
Valid Abort
B
Missing Battery
C
Input Circuit # 1
D
Low Voltage (<19VDC)
E
Intelli-Fet lost
F
Abort, premature
-
AC Power Brown-Out (<85%)
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
OPERATIONS
POWER
LIMITED
8
9
10
11
12
13
14
15
16
17
18
-
+
-
+
-
+
-
+
-
+
-
PUT
AUDIBLE #1
AUDIBLE #2
AUDIBLE #3
AGENT RELEASE
SOLENOID
MODULE
DIAGNOSTIC
LED
AC NORMAL
ALARM
T4
PRE-DISCHARGE
RELEASE
SUPERVISORY
TROUBLE
ALARMS SILENCED
ABORT
Code
Status
with
period
1.
Activated
2.
Activated
3.
Activated
4.
Activated
5.
Shorted
6.
Shorted
7.
Shorted
8.
Shorted (or initiator open)
9.
Shorted
C.
Input Circuit # 2
E.
5VDC Reference/A-D Failure
F.
Abort, Late
-.
Auxiliary Power In (<15VDC)
Page 29 of 43
Rev. No. 3, 04/02
RELEASE
CIRCUITS
SW4
SILENCE
RESET
R