EQUIPMENT
DETECTION BASE COMPATIBILITY
Fike P/N
Size
Char.
Ω Ω Ω Ω
67-1034
6"
430
67-1036
4"
430
C02-1164
6"
390
67-1035
6"
220
67-1037
4"
220
67-1026
6"
470
67-1029
4"
470
67-1031**
6"
0
NOTE: If using LED graphic, it is required to use the older type bases as listed in Section 3.2.
Please note on the order, "Using conventional graphic with panel, do not substitute bases".
DETECTOR COMPATIBILITY
NOTE: Use Hochiki detectors with Hochiki bases and System Sensor detectors with System
Sensor bases.
HOCHIKI
Fike
Type
P/N
63-1024
Photoelectric
63-1025
Photo/Heat
67-1033
Ionization
60-1029
Thermal, 135 w/Rate of Rise
60-1030
Thermal, 190 w/Rate of Rise
63-032
Photoelectric, Baseless
60-1020
Thermal, 135 Fixed Temp
60-1022
Thermal, 190 Fixed Temp
Page 16 of 43
Rev. No: 3, 04/02
Manufacturer
Mfg. P/N
Hochiki
NS6-224
Hochiki
NS4-224
Hochiki
HS-221D
Hochiki
NS6-220
Hochiki
NS4-220
System Sensor
B401BR470
System Sensor
B110RLP
System Sensor
B401B
Mfg. P/N
SLR-24
SLR-24H
SIJ-24
DCD-135
DCD-190
SLR-835B-2
AL-DFE-135
AL-DFE-190
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
FIKE CORPORATION
Maximum Bases per Circuit
Single
Sequential
Cross
Detector
Zone
Release
25
25
None
25
25
None
None
25
None
None
25
25
None
25
25
25
25
None
25
25
None
None
25
25
SYSTEM SENSOR
Fike P/N
Type
63-1015
Photoelectric
63-1017
Photo/Heat
67-1025
Ionization
60-1027
135 Thermal
63-1014
Photoelectric
67-1023
Ionization
Mfg. P/N
2451
2451TH
1451
5451
2151
1151
UL S2203