EQUIPMENT
60-1020 Heat Detector 135° ° ° ° F / Fixed Temperature
60-1022 Heat Detector 190° ° ° ° F / Fixed Temperature
The heat detector is suited for installation where high heat output fires are expected
or in areas where ambient conditions would not allow use of other detection
methods. Each detector is fixed temperature rated for 135°F (60-1020) where
ambient temperatures do not exceed 120°F or 190°F (60-1022) where ambient
temperatures exceed 120°F but not 160°F. Features mechanically operated contact
closures. Contact is not latching.
60-1029 Heat Detector 135° ° ° ° F / Rate-of-Rise
60-1030 Heat Detector 190° ° ° ° F / Rate-of-Rise
The fixed temperature / rate-of-rise heat detector features electronic circuitry to
close normally open contacts when the fixed temperature is reached or when the
rate-of-rise is greater than 12°F / minute.
Warning: Heat detectors are for property protection only, not life safety!
67-1034 6" Base
Electronics-free 6" base with plastic tamper-lock lug. Contains a 430Ω resistor. Can
be used for Sequential or Cross Zone detection.
67-1036 4" Base
4" version of the 67-1034
67-1035 6" Base
Electronics-free base with plastic tamper-lock lug. Contains a 220Ω resistor. Can
be used with Cross Zone or Single Detector Release detection.
67-1037 4" Base
4" version of the 67-1035
63-1012 Relay Base
This 6" base is equipped with a 430Ω resistor and two sets of Form "C" relay
contacts.
3.3
OUTPUT DEVICE
Refer to FIKE Notification Appliance and Releasing Compatibility Document (06-186).
Page 12 of 43
Rev. No: 3, 04/02
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
FIKE CORPORATION
UL S2203