Wiring Verification; System Module Installation; System Configuration - Fike SHP 10-051 Product Manual

Conventional fire alarm/suppression system
Table of Contents

Advertisement

FIKE CORPORATION
4.3

WIRING VERIFICATION

After pulling the wire into the enclosure, verify wire for ground-fault absence and acceptable impedances
prior to connecting the initiating and indicating circuits.
CAUTION: Field devices shall not be connected if using meggar or any means that applies
voltages in excess of device ratings (to prevent damage to the devices).
Input Circuits:
1. Verify no stray voltages exist on any field wiring prior to device installation.
2. Verify each conductor is free from shorts between all other conductors and chassis.
3. Measure wire resistance with a short across loop at point furthest from circuit start. This is
typically across EOL for Class B and back at panel for Class A. Verify per these limits:
Input1, Input2: Detector Circuits
Input3, Input4: Contact Monitor Circuits
Output Circuits:
1. Verify no stray voltages exist on any field wiring prior to device installation.
2. Verify each conductor is free from shorts between all other conductors and chassis.
3. Measure loop impedance with a short across loop at point furthest from circuit start. This is typically
across EOL for Audible 1-3 and Agent Release Module, and across solenoid for the solenoid output.
Verify per these limits:
Max Current (Amps)
Audibles 1-3 (Max Ωs)
Agent Release (Max Ωs)
Solenoid (Max Ωs)
4.4

SYSTEM MODULE INSTALLATION

Install system modules after the enclosure has been installed and cleaned of all dust and debris.
Modules include the appropriate mounting hardware. Prior to handling or installing any modules,
appropriate anti-static procedures must be followed per Section 1.6.
Transformer:
The transformer mounts to the four standoffs to the right of the AC terminal block.
Align on the standoffs and attach with four 6-32 screws and washers. Wire
transformer per Section 4.6, Wiring Diagram.
SHP Controller:
The SHP Controller mounts on the five standoffs in the upper half of the
enclosure. Secure using the four 6-32 nuts & four lock washers provided.
NOTE: Do not install a nut on the center standoff. Doing so could cause a ground fault.
SRM4:
The optional SRM4 mounts on the four standoffs on the SHP's lower right hand
corner. Align using standoffs, press and secure into place.
Class-A Module:
The optional Class-A module mounts directly above the initiating circuits. Align
using standoffs, press and secure into place.
4.5

SYSTEM CONFIGURATION

For the given installation, verify the SW3 configuration switches are set appropriately. Use the switch
setting information and configurations as listed in Section 4.7.
NOTE: If using 0 Ω detector bases or contact closure devices on Input 1 or Input 2 circuits, clip
the pertinent "0 Ω jumper". Clipping this jumper limits the current to 100 mA for the associated
circuit.
UL S2203
FM 0Z8A0.AY
Less than:
Less than:
0.1
0.2
0.3
0.4
0.5
24
12
8
6
4.8
35
35
35
35
35
12
6
4
3
2.4
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
INSTALLATION
20 Ωs
100 Ωs
0.6
0.8
1.0
1.5
2.0
4.0
3.0
2.4
1.6
1.2
35
35
35
35
35
2.0
1.5
1.2
0.8
0.6
Rev. No. 3, 04/02
Page 23 of 43