Specifications - Fike SHP 10-051 Product Manual

Conventional fire alarm/suppression system
Table of Contents

Advertisement

FIKE CORPORATION
3.6

SPECIFICATIONS

Environmental:
All electronics are rated 32° - 120°F (0° - 49°C) 85% relative humidity
Primary Input AC Power:
120 VAC, 50/60 Hertz, 1.42 Amps, 170 VA
208/240VAC, 50/60 Hertz, 0.82 Amps @ 208VAC, 0.71 Amps @ 240VAC, 170 VA
System AC line power must originate from a dedicated circuit at the main building power distribution
center. The circuit breaker shall be equipped with a lockout mechanism and be clearly labeled as a "Fire
Protection Control Circuit."
10-2171 Controller Board:
The controller's internal power supply provides 2.6 amps of 24VDC power. Power consumption of the
controller itself is 90ma at 24VDC in the normal standby mode.
8 " high x 11.5" wide x 2" deep; (1.2 lbs).
P1 - Power Supply Input:
TERMINAL
DESCRIPTION
1-2
Transformer
24 VAC
secondary
3-4
BAT +
Standby Battery
COM
4-5
Optional Auxiliary
COM
input power supply
AUX +
NOTE: Standby Batteries and Auxiliary Power input share the same negative (common
ground) input.
P2 – Input Circuits:
TERMINAL
DESCRIPTION
19-20
INPUT #1
Detection inputs
21-22
INPUT #2
23-24
INPUT #3
Contact closure
25-26
inputs
INPUT #4
UL S2203
FM 0Z8A0.AY
NOMINAL RANGE
22-28VAC
non-power limited
20.4-28VDC
non-power limited
20-28VDC
non-power limited
WIRING
Power limited
Class B
(Class A with optional
10-2172 module)
4.3 K EOL resistor
Power limited
Class B
(Class A with optional
10-2172 module)
4.3 K EOL resistor
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
SPECIFICATION DETAILS
Sealed lead-acid batteries only.
18 amp-hour maximum.
Maximum supply current: 8 amps/ 27VDC
Maximum charge current: 1.5 amps/
27VDC
Requires regulated source, UL listed for
fire protective signaling
Maximum supply current: 8 amps/24VDC
Maximum ripple: 0.100 Volts rms
SPECIFICATION DETAILS
Used for conventional detectors listed with
this panel (see next section) or contact
closure type detectors listed for fire alarm
use.
20 Ω maximum wire resistance
Used for contact closure inputs such as
Manual Release, Abort, Waterflow and
Supervisory listed for fire alarm use.
100 Ω maximum wire resistance
Page 15 of 43