Fike SHP 10-051 Product Manual page 33

Conventional fire alarm/suppression system
Table of Contents

Advertisement

FIKE CORPORATION
SW3 CONFIGURATION
The operation characteristics of the SHP system is determined by the configuration dip switches located
on the SHP Controller (SW3). These switches allow you to field define the operation of the SHP.
NOTE: Bold values indicate default positions (0001 1000 01) in S1 to S10 order. 0=off. Default
position only has switch positions S4, S5, & S10 on. All others are off.
Switch
0 = Off
Position
1 = On
0
Suppression System Mode
S1
1
Sprinkler System Mode
S2
0
Sequential Alarm Detection
1
Cross-Zone Detection
S5/S6
0/0
Pre-discharge Delay
0/1
1/0
1/1
S8
0
Pre-discharge / Sequential Alarm options per Table 4.7
1
Supervisory / Manual Release options per Table 4.7
S9
0
Unused (leave in the off position)
S10
0
Auxiliary 24 volt power input supervised
1
Auxiliary 24 volt power input supervision disabled
Dip switch positions S3, S4 and S7 allow you to adjust certain characteristics of the SHP panel as it
pertains to each operational mode (suppression versus sprinkler). The function of these switches varies
according to the setting of dip switch S1.
Switch
0 = Off
Position
1 = On
S3/S4
0/0
0/1
1/0
1/1
S7
0
1
ABORT TYPES:
These abort types are programmable via SW3 configuration switches S3-S4. Countdown does not begin
until the system is in the predischarge state.
TYPE 1: The abort is effective only if active upon entry into predischarge state. Countdown continues
during abort activation. Upon abort deactivation (during predischarge), the release cannot again be aborted,
so release occurs upon countdown completion. Conforms to Industrial Risk Insurers (IRI) requirements.
TYPE 2: Countdown continues during abort activation. Release occurs when both the countdown is
completed and the abort is deactivated.
TYPE 3: If the abort is active during predischarge, release occurs upon abort deactivation.
TYPE 4: Upon abort deactivation, countdown occurs from the full programmed countdown time. Prior to
countdown completion, abort activation extends the countdown time to the programmed length. Does not
conform to UL requirements, but is allowed by some Local Authority having Jurisdiction. Type 4 with "0"
countdown also provides "NYC mode" as described in the note below.
NOTE: The ABORT switch delays releases initiated by automatic detection schemes. Releases
initiated by activated Manual Release input circuits override the Abort Switch.
NOTE: For Abort = 4 with countdown = 00, system operates in "NYC mode" with a 120 second
verification delay, then a 30 second countdown after each abort input deactivation. During the
120 second verification delay, the system emulates continuous abort activation. After the 120
second delay, the system starts a 30 second pre-discharge delay.
UL S2203
FM 0Z8A0.AY
Operational Characteristic
= 00 Seconds
= 15 Seconds
= 30 Seconds
= 60 Seconds
Suppression Mode (S1 = Off)
Abort Type
= 1
= 2
(see appendix A
for description of
= 3
abort types).
= 4
ARM-III Operation
12 volt solenoid operation
SHP Product Manual
Manual P/N: 06-130
firealarmresources.com
INSTALLATION
Sprinkler Mode (S1 = On)
Solenoid On
= Continuous
Time
= 4-5 Min.
= 9-10 Min.
= 29-30 Min.
Not Applicable (Unused)
Page 27 of 43
Rev. No. 3, 04/02