T w i n f l e x P r o ² c o n v e n t i o n a l E x p a n s i o n C a r d 5 0 5 - 0 0 0 7

General Description

The TwinflexPro² Conventional Expansion card will provide 4 conventional zones. Therefore a TwinflexPro²
panel fitted with a Conventional Expansion card would have zones 1 to 4 as Twinflex zones and zones 5 to 8 as
conventional zones. The card is only compatible with the 4-zone TwinflexPro² panel. It is not compatible with the
2-zone TwinflexPro² panel or with any earlier TwinflexPro or TWINFLEX
Note: conventional zones cannot distinguish between smoke or MCP fire signals.

Installation

The panel must be completely powered down before this card is fitted.
1. Remove the right hand cover moulding from the unit by unscrewing the two fixing screws.
2. Next disconnect the battery by removing one of the push on battery leads at the battery. Always disconnect
the battery first before removing the mains power to the panel.
NOTE: Do not disconnect the battery by removing the wires from the terminals on the CIE circuit
board. Doing this may allow the batteries to short circuit.
3. Remove mains power from the panel by removing the fuse in the fused spur that supplies the panel or
switching off the circuit breaker. At this stage there should be no LEDs lit on the panel and the display
should be blank.
4. Disconnect all cabling from the CIE terminals. Make sure these cables are suitably labelled to facilitate
correct re-connection after fitting the Expansion Card.
5. Unscrew the four fixing screws that secure the left hand CIE assembly (Fig 1), then flip the assembly over
clockwise (Fig 2).
Fig 1
I N S TA L L AT I O N A N D M A I N T E N A N C E
I N S T R U C T I O N S
®
Checkpoint Plus panels.
26-1509 Issue 2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TwinflexPro2 conventional Expansion Card and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Fike TwinflexPro2 conventional Expansion Card

  • Page 1 I N S TA L L AT I O N A N D M A I N T E N A N C E I N S T R U C T I O N S T w i n f l e x P r o ² c o n v e n t i o n a l E x p a n s i o n C a r d 5 0 5 - 0 0 0 7 General Description The TwinflexPro²...
  • Page 2 Secure the expansion card PCB to the unit’s base using the 4 off M3 x 6 screws supplied (Fig 3). Please note the orientation of the expansion card PCB. 7. Plug one end of the ribbon cable assembly into the expansion card PCB (this will only fit one way). 8.
  • Page 3 Conventional Device Zones: Z5 - Z8: ✗ DO NOT SPUR (wiring not monitored) Z5 + Z5 - SCRN END OF LINE DIODE SMOKE MANUAL SMOKE MANUAL SMOKE OR HEAT CALL OR HEAT CALL OR HEAT DETECTOR POINT DETECTOR POINT DETECTOR Detector bases with integral continuity diodes must be used to ensure manual call points remain operational when a detector head is removed from its base.
  • Page 4: Technical Data

    Fike’s policy is one of continual improvement and the right to change a specification at any time without notice is reserved. Whilst every care has been taken to ensure that the contents of this document are correct at time of publication, Fike shall be under no liability whatsoever in respect of such contents.