Goodrive30 Series VFD
Function
Name
code
Sequence
of switching
running-co
mmand
P07.03
channels by
pressing
QUICK/JO
G
Stop
function
P07.04
validity of
STOP/RST
code from right to left.
3: Switch between FWD and REV rotating. Press
QUICK/JOG to shift the direction of the
frequency commands. This function is only valid
in the keypad command channels.
4: Clear the UP/DOWN setting. Press
QUICK/JOG to clear the set value of
UP/DOWN.
5: Coast to stop. Press QUICK/JOG to coast to
stop.
6: Switch command channels in sequence.
Press QUICK/JOG to shift the reference manner
of running commands in sequence.
7: Quick commissioning mode (based on
non-default parameter)
Note: Press QUICK/JOG to shift between
forward rotation and reverse rotation, the VFD
does not remember the state after shifting during
powering off. The VFD will run in the running
direction set in P00.13 during next powering on.
When P07.02=6, set the sequence of switching
running-command channels by pressing this key.
0: Keypad→Terminal→Communication
1: Keypad←→Terminal
2: Keypad←→Communication
3: Terminal←→Communication
The function code specifies the stop function
validity
of
STOP/RST.
STOP/RST is valid in any conditions.
0: Valid only for keypad control
1: Valid both for keypad and terminal control
2: Valid both for keypad and communication
control
3: Valid for all control modes
Description
For
fault
-75-
Function parameter list
Default
0
reset,
0
Modify
○
○
Need help?
Do you have a question about the Goodrive30 VFD Series and is the answer not in the manual?
Questions and answers