Goodrive30 Series VFD
Function
Name
code
FWD/REV
running
P01.14
switching
mode
P01.15 Stop speed 0.00–100.00Hz
Stop speed
P01.16
detection
mode
Feedback
speed
P01.17
detection
time
Terminal-ba
sed running
P01.18
command
protection
at power-on
The function code is used to set the switching
threshold of the VFD.
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop speed
with a delay
0: Detect by the set speed (without stop delay)
1: Detect by the feedback speed (only valid for
vector control)
When P01.16=1, the feedback frequency of the
VFD is less than or equal to P01.15 and is
detected during the time set by P01.17, the VFD
will stop; otherwise, the VFD stops in the time set
by P01.17.
Frequency f
Ramp reference
frequency
Stop speed
Running A
Running B
Running C
Setting range: 0.00–100.00s (only valid when
P01.16=1)
When the channel of running commands is
terminal control, the system detects the state of
the running terminal during power-on.
0: The terminal running command is invalid at
power-on. Even the running command is
considered as valid during power-on, the VFD
does not run and it keeps the protection state
until the running command is canceled and
enabled again.
1: The terminal running command is valid at
power-on. If the running command is considered
as valid during power-on, the VFD is started
automatically after the initialization.
Note: Exercise caution before using this
Description
Output frequency
C
B
A
P01.24
P01.17
-43-
Function parameter list
Default
0
0.50 Hz
1
0.50s
Time t
0
Modify
◎
◎
◎
◎
○