2.3 Wire size

The wiring and installation methods must conform to the national and local electrical code requirements.
PV wire size
The PV array's output current varies with size, connection method, and sunlight angle. Its ISC (short
circuit current) can calculate the minimum wire size. Please refer to the ISC value in the PV module's
specifications. When the PV modules are connected in series, the total ISC equals any PV module's ISC.
When the PV modules are connected in parallel, the total ISC equals the sum of all the PV module's ISC.
The PV array's ISC must not exceed the controller's maximum PV input current. For max. PV input
current and max. PV wire size, please refer to the table below:
Model
Tracer5415AN
Tracer5420AN
Tracer6210AN
Tracer6415AN
Tracer6420AN
Tracer8415AN
Tracer8420AN
Tracer10415AN
Tracer10420AN
The total voltage must not exceed the max when the PV modules are connected in
series. PV open circuit voltage (Tracer**10AN)/138V
CAUTION
(Tracer**15AN)/180V(Tracer**20AN)at 25 environment temperature.
Battery wire size
The battery wire size must conform to the rated current. The reference size is as below:
Model
Tracer5415AN
Tracer5420AN
Tracer6210AN
Tracer6415AN
Tracer6420AN
Tracer8415AN
Tracer8420AN
Tracer10415AN
Tracer10420AN
Max. PV input current
50A
60A
80A
100A
Rated charging current
50A
60A
80A
100A
7
Max. PV wire size
2
16mm
/6AWG
2
16mm
/6AWG
2
25mm
/4AWG
2
35mm
/2AWG
Battery wire size
2
16mm
/6AWG
2
16mm
/6AWG
2
25mm
/4AWG
2
35mm
/2AWG