Tracer10420AN

2.3 Wire size

The wiring and installation methods must conform to the national and local electrical code
requirements.
PV wire size
The PV array's output current varies with its size, connection method, and sunlight angle.
The minimum wire size can be calculated by its ISC(short circuit current). Please refer to
the ISC value in the PV module's specifications. When the PV modules are connected in
series, the total ISC is equal to any PV module's ISC. When the PV modules are connected
in parallel, the total ISC is equal to the sum of all the PV module's ISC. The PV array's ISC
must not exceed the controller's maximum PV input current. For max. PV input current and
max. PV wire size, please refer to the table as below:
Model
Tracer5415AN
Tracer5420AN
Tracer6210AN
Tracer6415AN Tracer6420AN
Tracer8415AN
Tracer8420AN
Tracer10415AN
Tracer10420AN
When the PV modules are connected in series, the total voltage must not exceed
the max. PV open circuit voltage
(Tracer**10AN)/138V(Tracer**15AN)/180V(Tracer**20AN)at 25 environment
temperature.
Battery wire size
The battery wire size must conform to the rated current, the reference size as below:
3000W/36V
4000W/48V
1250W/12V
2500W/24V
100A
3750W/36V
5000W/48V
Max. PV input current
4500W/36V
6000W/48V
1875W/12V
3750W/24V
5625W/36V
7500W/48V
50A
60A
80A
100A
14
180V(25℃)
Max. PV wire size
2
16mm
/6AWG
2
16mm
/6AWG
2
25mm
/4AWG
2
35mm
/2AWG