2.3 Wire Size

The wiring and installation methods must conform to all national and local electrical code
requirements.
PV Wire Size
Since PV array output can vary due to the PV module size, connection method or sunlight angle,
the minimum wire size can be calculated by the Isc
the PV module specification. When PV modules connect in series, the Isc is equal to a PV modules
Isc. When PV modules connect in parallel, the Isc is equal to the sum of the PV module's Isc. The
Isc of the PV array must not exceed the controller's maximum PV input current. Please refer to the
table as below:
NOTE: All PV modules in a given array are assumed to be identical.
*Isc=short circuit current(amps) Voc=open circuit voltage.
Model
TRIRON1206N
TRIRON1210N
TRIRON2206N
TRIRON2210N
TRIRON3210N
TRIRON3215N
TRIRON4210N
TRIRON4215N
*These are the maximum wire sizes that will fit the controller terminals.
When the PV modules connect in series, the open circuit voltage of the PV array
must not exceed 46V (TRIRON**06N), 92V (TRIRON**10N) or 92V
CAUTION
(TRIRON**15N) at 25℃ environment temperature.
Battery and Load Wire Size
The battery and load wire size must conform to the rated current, the reference size as below:
Model
TRIRON1206N
TRIRON1210N
Max. PV input current
Rated charge
discharge
current
10A
of PV array. Please refer to the value of Isc in
10A
20A
30A
40A
Rated
Battery wire size
current
10A
4mm
11
Max. PV wire size
2
4mm
/12AWG
2
6mm
/10AWG
2
10mm
/8AWG
2
16mm
/6AWG
Load wire size
2
/12AWG
4mm
2
/12AWG