Helios PD2-6100 Strain Gauge, Load Cell, and mV Meter

Strain Gauge Input

Inputs
Field selectable: 0-15 mV, 0-30 mV,
0-150 mV, 0-300 mV, ±15 mV, ±25 mV,
±150 mV, ±250 mV, or Modbus PV (Slave)
Isolated
Terminals EX+ & EX-: 10 VDC or
5 VDC  10%, rated @ 350 mA max.
Sensor Power
Supply
Note: Do not use 24 VDC to power strain
gauge bridge.
Accuracy
±0.03% of calibrated span ±1 count
14 Ω @ 5 V
Minimum
28 Ω @ 10 V
Load
Resistance
Maximum
350 mA @ 5 V or 10 V
Excitation
Current
Temperature
0.002% of calibrated span/C max from
Drift
0 to 65C ambient, 0.005% of calibrated
span/C max from -30 to 0C ambient
Functions
Linear with multi-point linearization
Multi-Point
2 to 32 points for PV or PV1
Linearization
2 to 8 points for PV2 (Dual-scale feature)
Low
0.1 to 999,999 (0 disables cutoff function).
Cutoff
Point below at which display always shows
zero.
Decimal Point Up to five decimal places or none:
d. d dddd, d. d ddd, d. d dd, d. d d, d. d , or dddddd
Calibration
Input
Range
Range
15 mV
25 mV, 30 mV
150 mV
250 mV, 300 mV
An Error message will appear if the input 1
and input 2 signals are too close together.
Input
Strain Gauge Bridge: Greater than 10 MΩ
Impedance
mV Source: 200 kΩ

Relays

Rating
Noise
Suppression
Deadband
High or Low
Alarm
Relay
Operation
Relay Reset
(Acknowledge)
Time Delay
Minimum Span
Input 1 & Input 2
0.2 mV
Fail-Safe
0.4 mV
Operation
2.0 mV
4.0 mV
Auto
Initialization

USB Connection

Function
Compatibility USB 2.0 Standard, Compliant
Connector
Type
Cable
Driver
Power
9
Instruction Manual
4 SPDT (Form C) internal and rated 3 A
@ 30 VDC and 125/250 VAC resistive load;
1/14 HP (≈ 50 W) @ 125/250 VAC for
inductive loads
Noise suppression is recommended for
each relay contact switching inductive
loads; see Switching Inductive Loads on
page 19 for details.
0-100% of span, user programmable
User may program any alarm for high or
low trip point.
Unused alarm LEDs and relays may be
disabled (turn off).
Automatic (non-latching) and/or
manual reset
Latching (requires manual
acknowledge) with or without clear
Pump alternation control (2 to 4 relays)
Sampling (based on time)
Off (disable unused relays and enable
Interlock feature)
Manual on/off control mode
User selectable via front panel button, F4
digital input, external contact closure on
digital inputs, or through serial
communications.
0 to 999.9 seconds, on & off relay time
delays. Programmable and independent for
each relay
Programmable and independent for each
relay.
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will
go to alarm state.
When power is applied to the meter, relays
will reflect the state of the input to the meter.
Programming only
Type B receptacle
USB Type A-B cable
®
®
Microsoft
Windows
XP/Vista/7/8/10
USB port provides power to the meter.
DO NOT apply AC or DC power to the
meter while the USB port is in use.