Programming Set And Reset Points; Setting Fail-Safe Operation; Programming Time Delay; Relay And Alarm Operation Diagrams - Helios PD2-6100 Instruction Manual

Strain gauge, load cell, and mv meter
Table of Contents

Advertisement

Helios PD2-6100 Strain Gauge, Load Cell, and mV Meter
Programming Set and Reset
Points
High alarm indication: program set point above reset
point.
Low alarm indication: program set point below reset
point.
The deadband is determined by the difference
between set and reset points. Minimum deadband is
one display count. If the set and reset points are
programmed with the same value, the relay will reset
one count below the set point.
Note: Changes are not saved until the reset point has
been accepted.

Setting Fail-Safe Operation

In fail-safe mode of operation, the relay coil is
energized when the process variable is within safe
limits and the relay coil is de-energized when the
alarm condition exists. The fail-safe operation is set
independently for each relay. Select on to enable or
select off to disable fail-safe operation.

Programming Time Delay

The On and Off time delays may be programmed for
each relay between 0 and 999.9 seconds. The relays
will transfer only after the condition has been
maintained for the corresponding time delay.
The On time delay is associated with the set point.
The Off time delay is associated with the reset point.
Relay and Alarm Operation
Diagrams
The following graphs illustrate the operation of the
relays, status LEDs, and ACK button.
High Alarm Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. To
detect a new alarm condition, the signal must go below the set point, and then go
above it.