Helios PD2-6100 Strain Gauge, Load Cell, and mV Meter
Isolated 4-20 mA Transmitter
Output
Output
Process variable (PV), max, min, set points
Source
1-4, Modbus input, or manual control mode
Scaling
1.000 to 23.000 mA for any display range
Range
Calibration
Factory calibrated:
0.00 to 100.00 = 4-20 mA output
Analog
1.000 mA minimum and 23.000 mA
Output
maximum for all parameters: overrange,
Programming
underrange, max, min, and break
Accuracy
± 0.1% of span ± 0.004 mA
Temperature
0.4 µA/C max from 0 to 65C ambient,
Drift
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from
input drift.
Terminals I+ & R: 24 VDC  10% isolated
Isolated
Transmitter
from the input at >500 V. May be used to
Power Supply
power the 4-20 mA output or other devices
(except load cell/strain gauge). Refer to
Connectors Labeling on page 16 and
Figure 29. 4-20 mA Output Connections on
page 21.
All models rated @ 40 mA max.
External Loop
35 VDC maximum
Power Supply
Output Loop
Power supply
Resistance
24 VDC
35 VDC
(external)
Additional
The
PD659-1MA-2MA
4-20 mA
4-20 mA output into two isolated 4-20 mA
Outputs
outputs
0-10 VDC
The
PD659-1MA-1V
optional 4-20 mA output to a 0-10 VDC
Output
output

RS-485 Serial Communications

Compatibility EIA-485
Connectors
Removable screw terminal connector
Max Distance 3,937' (1,200 m) max
Status
Separate LEDs for Power (P), Transmit
Indication
(TX), and Receive (RX)
Minimum Maximum
10 
700 
100 
1200 
can split the optional
can convert the
10
®
Modbus
RTU Serial
Communications
1 – 247 (Meter address)
Slave ID
300 – 19,200 bps
Baud Rate
Transmit
Programmable between 0 and 199 ms
Time Delay
Data
8 bit (1 start bit, 1 or 2 stop bits)
Parity
Even, Odd, or None with 1 or 2 stop bits
0.01 – 2.54 second
Byte-to-Byte
Timeout
Turn Around
Less than 2 ms (fixed)
Delay
Note: Refer to the Helios Modbus Register Tables located
at
www.predig.com
for details.

Digital Input (F4)

Function
Operate tare function, remote operation of
front-panel buttons, acknowledge/reset
relays, reset max/min values. See Function
Keys & Digital I/O Available Settings on
page 47 for a complete list of capabilities.
Contacts
3.3 VDC on contact. Connect normally
open contacts across F4 to COM
Logic Levels
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC

MeterView Pro Software

Availability
Download directly from meter or from
www.predig.com/download_software
®
System
Microsoft
Windows
Requirements
Communications USB 2.0 (for programming only)
(Standard USB A to USB Type B)
RS-485 to USB converter
(programming, monitoring, and data
logging)
Configuration
Configure meters one at a time
Power
USB port provides power to the meter.