Display Functions & Messages - Helios PD2-6100 Instruction Manual

Strain gauge, load cell, and mv meter
Table of Contents

Advertisement

Helios PD2-6100 Strain Gauge, Load Cell, and mV Meter
Display Functions & Messages
The meter displays various functions and messages
during setup, programming, and operation. The
following table shows the main menu functions and
messages in the order they appear in the menu.
Display Functions & Messages
Display
Parameter
setup
Setup
Input
Input
Polar
Polar
uni
Unipolar
bi
Bipolar
range
Range
15 nmV
15 mV
25 nmV
25 mV
30 nmV
30 mV
150nmV
150 mV
250nmV
250 mV
300nmV
300 mV
ratio
Ratiometric
d-SCAL
Dual-Scale
units
Units
Dec pt
Decimal
point
PV 1
PV1
PV 2
PV2
prog
Program
SCALE
Scale
SCAL 1
Scale 1
SCAL 2
Scale 2
Action/Setting
Description
Enter Setup menu
Enter Input selection
menu
Enter unipolar or bipolar
selection menu
Press Enter to select
operation with positive
signals only
(e.g. 0-30 mV)
Press Enter to select
operation with positive &
negative signals
(e.g. ±15 mV)
Enter range selection
menu
Set meter for 15 mV
input (uni/bi)
Set meter for ±25 mV
input (bi)
Set meter for 30 mV
input (uni)
Set meter for 150 mV
input (uni/bi)
Set meter for ±250 mV
input (bi)
Set meter for 300 mV
input (uni)
Press Enter to select
ratiometric operation to
compensate for
excitation changes.
Press Enter to select
dual-scale display
(Select Yes or No)
Select the display
units/tags
Set decimal point
PV1 decimal point
(dual-scale)
PV2 decimal point
(dual-scale)
Enter the Program menu
Enter the Scale menu
Enter the Scale menu for
PV1
Enter the Scale menu for
PV2
25
Display Functions & Messages
Display
Parameter
Action/Setting
Description
Cal
Calibrate
Enter the Calibration
menu
Inp 1
Input 1
Calibrate input 1 signal
or program input 1 value
Dis 1
Display 1
Program display 1 value
Inp 2
Input 2
Calibrate input 2 signal
or program input 2 value
(up to 32 points)
Dis 2
Display 2
Program display 2 value
(up to 32 points)
Error
Error
Error, calibration not
successful, check signal
or programmed value
dsplay
Display
Enter the Display menu
Line 1
Line 1
Press Enter to assign the
upper display parameter
(default: PV)
Line 2
Line 2
Press Enter to assign the
lower display parameter
(default: engineering
units)
d-Inty
Display
Set display intensity level
intensity
from 1 to 8
RELaY
Relay
Enter the Relay menu
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic
reset
A-nman
Auto-
Set relay for automatic &
manual
manual reset any time
LatCH
Latching
Set relay for latching
operation
Lt-CLr
Latching-
Set relay for latching
cleared
operation with manual
reset only after alarm
condition has cleared
Altern
Alternate
Set relay for alternation
control
Sanmpl
Sampling
Set relay for sampling
operation
OFF
Off
Disable relay and front
panel status LED (Select
Off to enable Interlock
feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-4 setup.
FaiLSF
Fail-safe
Enter Fail-safe menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe
operation
on
On
Enable fail-safe
operation
Instruction Manual

Advertisement