Table 11. Relative humidity specifications
Relative humidity
Storage
Operating
Table 12. Maximum vibration specifications
Maximum vibration
Operating
Storage
Table 13. Maximum shock specifications
Maximum shock
Operating
Storage
Table 14. Maximum altitude specifications
Maximum altitude
Operating
Storage
Table 15. Operating temperature de-rating specifications
Operating temperature de-rating
Up to 35°C (95°F)
35°C to 40°C (95°F to 104°F)
40°C to 45°C (104°F to 113°F)

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility of the customer.
Table 16. Particulate contamination specifications
Particulate contamination
Air filtration
16
Technical specifications
Specifications
5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must
be non-condensing at all times.
10% to 80% relative humidity with 26°C (78.8°F) maximum dew point.
Specifications
0.26 G
at 5 Hz to 350 Hz (all operation orientations).
rms
1.87 G
at 10 Hz to 500 Hz for 15 min (all six sides tested).
rms
Specifications
Six consecutively executed shock pulses in the positive and negative x, y,
and z axes of 6 G for up to 11 ms.
Six consecutively executed shock pulses in the positive and negative x, y,
and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Specifications
3048 m (10,000 ft)
12,000 m (39,370 ft)
Specifications
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m
(3,117 ft).
Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m
(3,117 ft).
Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m
(3,117 ft).
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a
95% upper confidence limit.
NOTE:
This condition applies to data center environments only.
Air filtration requirements do not apply to IT equipment designed
to be used outside a data center, in environments such as an
office or factory floor.
NOTE:
Air entering the data center must have MERV11 or
MERV13 filtration.