4.2.1

Continuation of CP915 or CP924 installation

1. Connect the front plate to the control board and the power supply unit:
Connect a USB port (8) to the board for the touch sensor connection on the front plate. Appro-
priate connecting cable included in scope of delivery.
USB connection control board
2. Connect the screen output DVI (9) to the front plate.
DVI cable: Cable length < 3 m, connect firmly to PE on both sides. Appropriate DVI-D connect-
ing cable included in scope of delivery.
DVI-D connection control board
3. Connect the voltage supply to the power supply unit via the pre-assembled wiring. Connect
the earthing to the front plate.
Pre-assembled voltage supply
20
8
9