Transfer Time; Battery Temperature Sensor Operation; Figure 3-4, Bts Temperature To Charge Voltage Change - Magnum Energy Sensata MagnaSine Owner's Manual

Pure sine wave inverter/charger
Table of Contents

Advertisement

Operation

3.2.2 Transfer Time

While in Standby mode, the AC input is continually monitored. Whenever AC power falls below
the VAC dropout voltage (80 VAC per leg – default setting), the inverter automatically transfers
back to Inverter mode with minimum interruption to any connected appliances—as long as the
inverter is turned on. The transfer from Standby mode to Inverter mode occurs in approximately
16 milliseconds. While the MS-PAE Series is not designed as a computer UPS system, this transfer
time is usually fast enough to hold them up. However, the VAC Dropout setting has an effect on
the ability of the loads to transfer without resetting. The lower this setting, the longer the effective
transfer will be and therefore, the higher the probability for the output loads to reset. This occurs
because the incoming AC voltage is allowed to fall to such a low level that when the transfer does
occur (in addition to the relay transfer time) the voltage on the inverter's output has already fallen
to a low enough level to reset the loads.
The disadvantage of a higher VAC Dropout setting is that smaller generators (or large generators
with an unstable output) may nuisance transfer. This commonly happens when powering loads
that are larger than the generator can handle—causing the generator's output to constantly fall
below the inverter's input VAC dropout threshold.
Info: When switching from Inverter mode to Standby mode, the inverter waits
approximately 15 seconds before transferring to ensure the AC source is stable.
3.3

Battery Temperature Sensor Operation

The plug-in Battery Temperature Sensor (BTS) is used to determine the temperature around the
batteries. This information allows the multistage battery charger to automatically adjust the battery
charge voltages for optimum charging performance and longer battery life.
When the BTS is installed, the charge voltage while in the Bulk, Absorb or Float charge mode
will either increase or decrease if the battery temperature is greater or lower than 77°F (25°C).
If the temperature around the BTS is below 77°F (25°C) the charge voltage increases and if the
temperature around the BTS is higher than 77°F (25°C), the charge voltage decreases. The farther
the temperature change from 77°F (25°C), the greater the change in the charging voltage. See
Figure 3-4 to determine how much the charge voltage changes (increases or decreases) depending
on the temperature reading of the BTS. For example, the nominal absorb charge voltage for a
fl ooded battery at 77°F (25°C) on a 24-volt model is 29.2 VDC. If the battery temperature is 95°F
(35°C), the absorb charge voltage would decrease to 28.6 VDC (29.2 nominal – 0.6 change).
If the temperature sensor is NOT installed, the charge voltages will not be compensated and the
battery charges at a temperature of 77°F (25°C). Without the BTS installed, the life of the batteries
may be reduced if they are subjected to large temperature changes.
Info: The temperature to voltage compensation slope the BTS uses is 5mV/°C/Cell
from 0 to 50°C.

Figure 3-4, BTS Temperature to Charge Voltage Change

Page 34
Temperature Compensation using BTS
24VDC units
+1.5V
0.75
+1.2V
0.6
+0.9V
0.45
+0.6V
0.3
+0.3V
0.15
No Change
0
-0.3V
-0.15
-0.6V
-0.3
-0.9V
-0.45
-1.2V
-0.6
-1.5V
-0.75
0
5
1 0
1 5
0C
5C
10C
15C
32F
41F
50F
59F
Temperature reading from BTS (in degrees)
no BTS
connected
2 0
2 5
3 0
3 5
4 0
4 5
20C
25C
30C
35C
40C
45C
68F
77F
86F
95F
104F
113F
© 2017 Sensata Technologies
48VDC units
+3.0V
+2.4V
+1.8V
+1.2V
+0.6V
No Change
-0.6V
-1.2V
-1.8V
-2.4V
-3.0V
5 0
50C
122F

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mspae4448Ms4024pae

Table of Contents