CLEARANCES TO COMBUSTIBLE MATERIALS
N.B. This appliance must be installed in accordance with the instructions on the unit's certification.
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS FOR PSG FURNACES
45° ELBOW
FIGURE
N.B. THE AIR RETURN CONDUITS SHOULD BE AT LEAST EQUAL TO THE COLD AIR
PLENUM DIMENSIONS.
NOTE: THE HEIGHT OF THE PLENUM MUST BE 24 INCHES FOR THE FURNACES PSG 4000,
PSG 4500 AND PSG 5000.
CEILING
HOT AIR
SEE
PLENUM
BELOW
ELECTRIC
ELEMEMTS
Hot air plenum minimal height.
STATIC
PRESSURE
CHECK POINT
MIN. 0.20"W.C.
7
LEFT
WALL
24" BOTH SIDES FOR PSG5000
24" BOTH SIDES IF WITH OIL UNIT