(1) Select the cable run location so they are away from electrical equipment (motors, transformers,
or radio transmitters) which causes electromagnetic or electrostatic interference.
(2) Deterioration of flowmeter circuit insulation occurs if the converter interior or cable ends get wet
or humidified. This in turn causes malfunction of flowmeter or noise problems. Avoid a rainy
day if the flowmeter is to be installed outdoors. Even indoors, prevent water from splashing over
the flowmeter. Try to finish the wiring as quickly as possible
(3) The converter has a surge arrestor/protector installed inside. Therefore, do not conduct a
withstand voltage test for the converter. To check the insulation of the converter, use a voltage
of 250Vdc or less.
(4) After wiring, be sure to install the terminal block protection cover.

5.1 Cables

Use the kind of cables shown in Table 5.1 to wire the converter.
Name
3-core vinyl sheathed cable or 2-core vinyl
Power cable
sheathed cable
The number of conductors the cable contains differs depending on the
specification of the output signal cable.
Output signal
Use a shielded cable of finished outer diameter 11 to 13mm and nominal
cable
cross-sectional area 1.25mm
Table 5.1 Installation Cables
Cable name
.
2
− 27 −
Nominal
Finished
cross-sectional
outer
area
diameter
2 mm²
11~13mm
6 F 8 A 0 9 3 4
Description
CVV JIS C
3401,IEC60695,IEC607
54,IEC60227,IEC60245
or equivalent
CVV-S JIS -258-C or
equivalent