Output Low Limit Setting - Toshiba LF516 Instruction Manual

Electromagnetic flowmeter capacitance type
Table of Contents

Advertisement

Switch operation
STEP1
STEP2
STEP3
STEP4(=END)

8.2.17 Output Low Limit Setting

The low limit of the current output for converter can be set.
The output low limit can be selected from the items listed in the table below.
● Output low limit setting function
Selection items
4.0mA
3.2mA
2.4mA
Note: If the low cutoff value in 8.2.12 "Low Cutoff" is set to a value other than 0%, the output low
limit value will be fixed to 4.0mA, regardless of the set value.
Display example
ALM 4-20
UNDER 3mA
ESC
ALM 4-20
UNDER 3mA
ALM 4-20
4mA
ALM 4-20
4mA
SET OK?
ESC
N O
O K
Output low limit
The current value can be outputted up to 4.0mA (0%).
The current value can be outputted up to 3.2mA (−5%).
The current value can be outputted up to 2.4mA (−10%).
− 79 −
Description
The currently set value (UNDER 3.0mA in
this example) appears.
Then push
.
* Pushing
ESC
returns you to the setting
menu.
The switches at the bottom change.
(
At the same time, the cursor appears.
(The item indicated by the cursor is
highlighted.)
Then push
You can continue to change the setting item.
Push
to change the selection
items.
: Selected item is scrolled up.
: Selected item is scrolled down.
When the desired item is selected, push
to set the item temporarily.
When you push
, a message appears
to confirm whether the setting is OK or not.
If OK, push
. If you want to redo the
O K
setting, push
.
N O
Pushing
cancels the setting operation
ESC
and exits the setting screen.