6. Operating with DeviceNet Communications
Data
Name
Byte 0,
Terminal
bit 5
S6*
Byte 0,
Terminal
bit 6
S7*
Byte 1,
External
bit 0
Fault
Byte 1,
Fault Reset Resets the Inverter from fault status.
bit 1
Byte 1,
Terminal
bit 5
MA*
Byte 1,
Terminal
bit 6
P1
Inputs the function set for Inverter con-
stant n055 (Multi-function Input Selec-
tion 6.)
0: Terminal S6 function OFF
1: Terminal S6 function ON
Inputs the function set for Inverter con-
stant n056 (Multi-function Input Selec-
tion 7.)
0: Terminal S7 function OFF
1: Terminal S7 function ON
External fault (EF0) input from communi-
cations.
0: ---
1: External fault (EF0)
0: ---
1: Reset fault.
Operates the Inverter's multi-function
output terminal MA. This function is en-
abled only when Inverter constant n057
is set to 18.
0: Terminal MA OFF
1: Terminal MA ON
Operates the Inverter's multi-function
output terminal P1. This function is en-
abled only when Inverter constant n058
is set to 18.
0: Terminal P1 OFF
1: Terminal P1 ON
Contents
89