YASKAWA Varispeed V7 Instruction Manual page 154

Compact general-purpose inverter
Table of Contents

Advertisement

Voltage
Capacity
Class (V)
(kW)
400 V
0.37
3-phase
0.55
1.1
1.5
2.2
3.0
3.7
5.5
7.5
1. Reduce the continuous output current when changing the
NOTE
carrier frequency to 4 (10 kHz) for 200 V Class (1.5 kW
or more) and 400 V Class Inverters. Refer to the table
above for the reduced current.
Operation Condition
• Input power supply voltage:
• Ambient temperature:
2. If the wiring distance is long, reduce the Inverter carrier
frequency as described below.
Wiring Distance
between Inverter
and Motor
Carrier Frequency
(n080 setting)
3. Set the Carrier Frequency Selection (n080) to 1, 2, 3, or 4
when using vector control mode. Do not set it to 7, 8, or 9.
Factory Setting
Setting
Carrier Fre-
quency (kHz)
3
7.5
3
7.5
3
7.5
3
7.5
3
7.5
3
7.5
3
7.5
3
7.5
3
7.5
3-phase 200 to 230 V (200 V Class)
Single-phase 200 to 240 V (200 V Class)
3-phase 380 to 460 V (400 V Class)
−10 to 50°C (14 to 122°F)
(Protection structure: open chassis type IP20)
−10 to 40°C (14 to 105°F)
(Protection structure: top closed type IP20,
enclosed wall-mounted type NEMA 1 (TYPE 1))
Up to 30 m
Up to 50 m
14.5 kHz or
10 kHz or
less
less
(n080=5, 6)
(n080=1, 2,
3, 4, 7, 8, 9)
7. Programming Features
Maximum
Continuous
Output Cur-
rent (A)
1.2
1.8
3.4
4.8
5.5
7.2
8.6
14.8
18
Up to 100 m
5 kHz or
less
(n080=1, 2,
7, 8, 9)
Reduced
Current
(A)
1.0
1.6
3.0
4.0
4.8
6.3
8.1
14.8
17.0
More than
100 m
2.5 kHz or
less
(n080=1, 7,
8, 9)
153