YASKAWA Varispeed V7 Instruction Manual page 126

Compact general-purpose inverter
Table of Contents

Advertisement

Register
Number
002DH
Output status
Bit
002EH to
Reserved.
0030H
0031H
Main circuit DC voltage (1/1 V)
0032H
Torque monitor (1/1%; 100%/Rated motor torque; signed)
0033H to
Not used.
0036H
0037H
Output power (100/1 KW; signed)
0038H
PID feedback value (100(%)/Input corresponding to max. output
frequency;10/1%; unsigned)
0039H
PID input value (±100(%)/±Max. output frequency; 10/1%; signed)
003AH
PID output value (±100(%)/±Max. output frequency; 10/1%;
signed)
003BH
Output current (10/1 A)
003CH to
Reserved.
00FFH
* The MA output signal can be used from DeviceNet communications only.
There is no corresponding external output terminal.
Constant Data
Inverter constants can be set or referenced. For the register numbers of
the constants, refer to the list of constants given on page 242.
6. Operating with DeviceNet Communications
0
*
MA
(1: Closed)
1
P1 (1: Closed)
2
P2 (1: Closed)
3
Not used.
4
Not used.
5
Not used.
6
Not used.
7
Not used.
8 to F
Not used.
Contents
125

Advertisement