YASKAWA Varispeed V7 Instruction Manual page 226

Compact general-purpose inverter
Table of Contents

Advertisement

Voltage Class
Model
3-
20P1
CIMR-
phase
*1
V7
C
Single-
B0P1
phase
Motor Over-
Electronic thermal overload relay
load Protec-
tion
Instanta-
Motor coasts to a stop at approx. 250% of Inverter rated current
neous
Overcurrent
Overload
Motor coasts to a stop after 1 minute at 150% of Inverter rated output cur-
rent
Overvoltage
Motor coasts to a stop if DC bus voltage exceed 410 V
Undervoltage
Stops when DC bus voltage is approx. 200 V or less (approx. 160 V or
less for single-phase series).
Momentary
Following items are selectable: Not provided (stops if power loss is 15 ms
Power Loss
or longer), continuous operation if power loss is approx. 0.5 s or shorter,
continuous operation.
Heatsink
Protected by electronic circuit.
Overheat
Stall Preven-
Can be set individual level during acceleration/deceleration, provided/not
tion Level
provided available during coast to a stop.
Cooling Fan
Protected by electronic circuit (fan lock detection).
Fault
Ground Fault
Protected by electronic circuit (overcurrent level).
Power
ON until the DC bus voltage becomes 50 V or less. RUN indicator stays
Charge Indi-
ON or Digital Operator indicator stays ON.
cation
Multi-
Seven of the following input signals are selectable: Forward/reverse run
func-
(3-wire sequence), fault reset, external fault (MA contact input), multi-step
tion
speed operation, JOG command, acceleration/deceleration time select,
Input
external baseblock (MA contact input), SPEED SEARCH command, AC-
CELERATION/DECELERATION HOLD command, LOCAL/REMOTE se-
lection, communication/control circuit terminal selection, emergency stop
fault, emergency stop alarm, UP/DOWN command, PID control cancel,
PID integral reset/hold
Multi-
Following output signals are selectable (1 MA contact output (See note
func-
3.), 2 photocoupler outputs):
tion
Fault, running, zero speed, frequency agree, frequency detection (output
frequency ≤ or ≥ set value), overtorque detection, undervoltage detection,
Output
minor error, baseblock, operating mode, Inverter run ready, fault retry, UV,
speed search, PID feedback loss detection
Standard
Voltage vector control, full-range automatic torque boost, slip compensa-
Functions
tion, DC injection braking current/time at startup/stop frequency reference
bias/gain, PID control, energy-saving control, constant copy, frequency
reference with built-in potentiometer, unit selection for frequency refer-
ence setting/display
200 V single-/3-phase
20P2
20P4
20P7
B0P2
B0P4
B0P7
10. Specifications
21P5
22P2
23P7
B1P5
B2P2
B3P7
25P5
27P5
-
-
225