2. This setting is not necessary unless read-prohibition is selected.
COPY Function
This function writes the constants stored inside the Digital Operator in
batch to the Inverter. Write-in is possible only for Inverters with the
same product series, power supply specifications, and control mode (V/
f control or vector control).
Therefore, writing from 200 V Class to 400 V Class Inverters (or vice
versa), from V/f control mode to vector control mode Inverters (or vice
versa), or from Varispeed V7 to VSmini J7 Inverters is not possible.
The Constant Copy Function Selection (n176), Constant Read Selection
Prohibit (n177), Fault History (n178), Software Version No. (n179), and
hold output frequency are not written. vAE will appear (flashing) if the
capacities of the Inverters differ.
Press ENTER to continue writing (the COPY function).
Press STOP/RESET to stop the COPY function.
The following constants are not written if the Inverter capacities differ.
Constant No.
n011 to n017
V/f Settings
n036
Motor Rated Current
n080
Carrier Frequency
Selection
n105
Torque Compensa-
tion Iron Loss
n106
Motor Rated Slip
n107
Line to Neutral (per
Phase)
Name
Constant No.
7. Programming Features
n108
Motor Leakage In-
ductance
n109
Torque Compensa-
tion Voltage Limiter
n110
Motor No-load Cur-
rent
n140
Energy-saving Coef-
ficient K2
n158
Motor Code
Name
189