YASKAWA Varispeed V7 Instruction Manual page 223

Compact general-purpose inverter
Table of Contents

Advertisement

Trouble
The motor speed is
unstable. The motor
speed fluctuates when
operating with a light
load.
The digital operator
does not turn ON.
222
Cause
The stall prevention level during
running is too low.
Because the stall prevention level
during running (n094) is too low, the
output current reaches the set level
and the speed drops.
The load is too heavy.
If the load is too heavy, stall
prevention is activated, the output
frequency is stopped, and the
acceleration time is lengthened.
The carrier frequency is too high.
If operating the motor with a light load,
a high carrier frequency may cause
the motor speed to fluctuate.
The V/f set value is too high for a
low speed operation.
Because the set value for the V/f is
too high, over-excitation occurs at low
speeds.
The maximum frequency and base
frequency were incorrectly
adjusted.
Example: To operate a 60 Hz motor at
40 Hz or less, the maximum
frequency and base frequency are set
to 40 Hz.
The inverter is used for an
operation at 1.5 Hz or less.
The analog reference input is
unstable and has noise
interference.
The power is not being supplied.
The breaker or other component on
the power input side is not turned ON,
and the power is being not supplied.
The digital operator is not correctly
mounted.
Because the digital operator is not
correctly mounted, the display does
not appear.
Corrective Actions
Check if the stall prevention level
during running (n094) is set to an
appropriate value.
Reduce the load.
Decrease the carrier frequency
(n080).
Set the V/f (n011 to 017) according to
the load characteristics.
Set the maximum frequency (n011)
and the base frequency (n013)
according to the motor specifications.
Do not use the V7 inverter for an
operation that runs at 1.5 Hz or less.
For an operation at 1.5 Hz or less,
use a different inverter model.
Increase the set value for the filter
time constant (n070).
Check if the power is being supplied.
Mount the digiral operator correctly.

Advertisement

Table of Contents
loading

Table of Contents