Byte
Bit 7
Bit 6
3
Speed Actual (High Byte)
Data
Name
Byte 0,
Faulted
bit 0
Byte 0,
Warning
bit 1
Byte 0,
Running 1
bit 2
(Fwd)
Byte 0,
Running 2
bit 3
(Rev)
Byte 0,
Ready
bit 4
6. Operating with DeviceNet Communications
Bit 5
Bit 4
Indicates that the Inverter detected a
fault.
0: Normal
1: Fault detected.
Indicates that the Inverter detected a
warning.
0: Normal
1: Warning detected.
Indicates the Inverter's operating status.
0: Stopped, operating in reverse, or
applying DC injection braking
(Reverse RUN command ON).
1: Operating forward or applying DC
injection braking (Reverse RUN com-
mand OFF).
Indicates the Inverter's operating status.
0: Stopped, operating forward, or apply-
ing DC injection braking (Reverse
RUN command OFF).
1: Operating in reverse or applying DC
injection braking (Reverse RUN com-
mand ON).
Indicates the Inverter's preparation sta-
tus.
0: Fault detected or initializing.
1: Preparations for operation completed.
Bit 3
Bit 2
Contents
Bit 1
Bit 0