Cleaning The Condensate Drain Line; Checking Csd-1 Manifold Flow Switch - Watts AERCO EXT Installation, Operation & Maintenance Manual

Modulex ufly controller commercial
Table of Contents

Advertisement

Modulex EXT Commercial Series
CHAPTER 8: Maintenance Schedule

8.3.1 Cleaning the Condensate Drain Line

In order to inspect and clean the condensate line, do the following:
1. Refer to Figure 8-1, disconnect the pipe at location "A".
2. Check that no deposits have accumulated inside the drain. If there are any deposits flush
them out with clean water.
3. Reassemble the drain in reverse order.
W A R N I N G !
Before operating the boiler, it is absolutely necessary to verify that the condensate P-trap is filled
with water. If the boiler is operated without the P-trap being properly filled, there is a danger of
toxic combustion gases escaping from the unfilled condensate drain opening.

8.4 Checking CSD-1 Manifold Flow Switch

Check the function of the flow switch in the CSD-1 manifold at the boiler hot water outlet. If it is
not functioning, check the wiring to terminals FL and 10 on the Input/Output box, or replace with
a new flow switch.
OMM-0160_A • DRAFT
Figure 8-1: Condensate Drain Location
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Page 98 of 117

Advertisement

Table of Contents
loading

Table of Contents