CHAPTER 8: Maintenance Schedule

6.7 BMM Parameters

This section provides the list of the parameters in the BMM (Burner Management Module) boards.
See Section 6.4 for instructions on how to navigate to the BMM parameters.
PARAMETER
DESCRIPTION
803
Enabled services - NOT APPLICABLE.
Note: Leave at default value of 1
48
CH#1: setpoint
(CH maximum target temperature)
784
Local BUS address
Note: DO NOT CHANGE the value as this
is automatically assigned on the bus chain
816
Modbus Address
817
Modbus Communication Timeout
896
Temperature unit
0: °C
1: °F
799
Analogue input function 0/10 V - NOT
APPLICABLE.
Note: Leave at default value of 0
376
Programmable Input #1 function
- NOT APPLICABLE.
Note: Leave at default value of 0
322
Pump Off Delay - NOT APPLICABLE.
Note: Leave at default value of 3 min.
341
Pump: minimum control - NOT
APPLICABLE.
Note: Leave at default value of 30%
313
Pump: maximum control - NOT
APPLICABLE.
Note: Leave at default value of 100%
31
CH#1: Minimum Setpoint
39
CH#1: Maximum Setpoint
792
CH Maximum modulation
619
Ignition Modulation
645
Flame stabilization time - NOT
APPLICABLE.
Note: Leave at default value of 0 sec
783
Burner: recycling - NOT APPLICABLE.
Note: Leave at default value of 0
OMM-0160_A • DRAFT
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
ENTRY RANGE
DEFAULT
68°F to 185°F
(20°C to 85°C)
Automatically
1-127
0 - 240 sec
See Description
68°F to 104°F
(20°C to 40°C)
113°F to 212°F
(45°C to 100°C)
0-100%
32-82%
MLX EXT 450 2S
-1100 2S: 55%
MLX EXT 1500 2S
-3000 2S: 50%
Page 88 of 117
1
176°F (80C)
assigned
1
30 sec
0
0
0
3 min
30%
100%
86°F
203°F
100%
0 sec
0