CHAPTER 4: Installation Instructions

4.7.2 Products to Avoid in the Boiler Room

Do NOT store the following in the boiler room and/or around combustion air intake vents.
Spray cans containing chlorocarbons/fluorocarbons
Ammonium and/or ammonium solutions
Permanent wave solutions
Chlorinated waxes and/or cleaners
Chlorinated swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents
Adhesives used to fasten building products
Other damaging or flammable products

4.8 Recommended Clearances for Servicing

Recommended clearances around the boiler are listed below (see Figure 4-4):
It is recommended to install the boiler with the clearances as shown above to be able to perform
normal service and cleaning operations. Minimum required clearances depend on the piping
and venting configuration. For further details, contact your local manufacturer's representative.
OMM-0160_A • DRAFT
Figure 4-4: MODULEX EXT Boiler Clearances
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
TOP of the boiler:
FRONT of the boiler:
UNVENTED side:
VENTED side:
FLOOR/GROUND:
REAR of the boiler:
FLOOR/GROUND:
BACK of the boiler:
24'' (609.6 mm)
24'' (609.6 mm)
24'' (609.6 mm)
32'' (813 mm)
4''
(100 mm)
24'' (609.6 mm)
4''
(100 mm)
24'' (600 mm)
Page 27 of 117