Bcm Parameters - Watts AERCO EXT Installation, Operation & Maintenance Manual

Modulex ufly controller commercial
Table of Contents

Advertisement

Modulex EXT Commercial Series
CHAPTER 8: Maintenance Schedule

6.6 BCM Parameters

This section provides the list of the parameters in the BCM. See Section 6.4 for instructions on
how to navigate to the BCM parameters.
PARAMETER
DESCRIPTION
Enabled services
16 = Control via Modbus*
17 = Heating only
18 = Antifreeze only
19 = Heating + Antifreeze
803
24 = DHW only
25 = Heating + DHW
26 = DHW + Antifreeze
27 = Heating + DHW + Antifreeze
* - Control via Modbus examples: AERCO ACS,
Remote Setpoint from BAS/EMS
Maximum Differential Temperature
483
(Water ΔT protection)
34
Burner Hysteresis
31
CH#1: Minimum Setpoint
39
CH#1: Maximum Setpoint
Analogue input function 0/10 V:
0 = Backup Controller (BCM) target
temperature
1 = External temperature sensor
799
2 = 0-10 V Remote Setpoint
3 = DO NOT USE
See Controls Manual OMM-0159 Sections 4.1.1,
4.3.2 and 6.3.1
Programmable Input #1 function
0 = CH Service Enable/Disable
1 = System Enable/Disable
2 = DO NOT USE
376
3 = Backup Controller (BCM) Remote
activation
See Controls Manual OMM-0159 Sections 4.5 and
6.3.2
322
Pump Off Delay
OMM-0160_A • DRAFT
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
ENTRY RANGE
DEFAULT
See Description
19
MLX EXT 450 2S
0°F/2°F – 90°F
-1100 2S: 45°F
(0°C/1°C-50°C)
(25°C)
0 = Disabled;
MLX EXT 1500 2S
Units may be expressed
-3000 2S: 54°F
in R or K
(30°C)
9°F to 36°F
(5°C to 20°C)
9°F (5°C)
Units may be expressed
in R or K
68°F to 221°F
86°F
(20°C to 105°C)
68°F to 221°F
185°F
(20°C to 105°C)
See Description
1
See Description
0
1 - 10 min
3 min
Page 84 of 117