Supervision system

The ASSA ABLOY RD3 and ASSA ABLOY RD4 have a built-in supervision system.
If an error occurs, the PCD display will show an error or status code. During normal operation the
display will show "ON".
To reset the door to normal operation after an error code, press C on the PCD. See code list below.

Code List

Code
Status
ON
The revolving door is func-
tioning normally
10
Stop
11
Electromechanical lock error
20
Emergency stop
21
Response from the PDR
sensor fitted above the
opening on the inside
22
Response from the PDR
sensor fitted above the
opening on the outside
25
Response from the touchless
door leaf sensors (the door
rotates slowly)
26
Response from the touchless
door leaf sensors (the door
stops)
30
Blocked door
31
Fire alarm
32
Power fail input
37
Emergency Open
C2
Break-out failure
C3
Break-out
For all other status codes, contact your ASSA ABLOY Entrance Systems service representative.
=
For contact information, see last page.
22
Cause
Safety edge activated
No signal from the elec-
tromechanical lock
Emergency stop button
pressed down
Inner PDR sensor activated
Outer PDR sensor activated
The detection zone of the
touchless door leaf sensors
activated
The detection zone of the
touchless door leaf sensors
activated
The wing is blocked by an
obstacle
The fire alarm system has, if
connected, been activated
Mains power lost
Emergency open push but-
ton pressed down.
No current to break-out
magnet
Break-out released
Issue 2020-10-09
Remedy
Check for obstacles between the wing and
the floor and between the wing and the
inside of the drum. Check safety edges.
Make one more unlock/lock operation. If
that does not help call
ASSA ABLOY Entrance Systems Service.
Release the button by turning it in the dir-
ection of the arrows, then restore function
by pressing C on the PCD.
Remove obstacle in the inner detection
zone
Remove obstacle in the outer detection
zone.
Remove obstacle in the detection zone.
Remove obstacle in the detection zone.
Check for obstacles between the wing and
the floor and between the wing and the
inside of the drum. After checking, press C
on the PCD.
Check the fire alarm system.
Check mains fuse.
Check external power supply.
Release the button by turning it in the dir-
ection of the arrows, then restore function
by pressing C on the PCD.
Call for service.
Close the door leaves.
Reset function by pressing C on the PCD.