"Zone from" and "Zone to" parameters are defining zones covered for the related events.
These parameters are not changeable for the alarms. User can change zone coverage only
for Relay-5.
Relay working mode such as latched or automatic is not defined per relay. This parameter is
defined per detector and alarm level. Hence if user wants to set relay in auto-reset or
latched, it should be defined via detector alarm settings.
7.4 Test Options:
DPX Series Control Panel provides artificial testing option to user to control connections and
event generation scenarios without using real gas. To run tests select "4.Test" option from
main menu:
Panel program will provide testing options:
Display test flashes all pixels of the display and activates all LEDs to make sure all are in
operation. Relay test is activates the relays that user can check whether switching outputs
and connected devices working as expected. Panel program will provide relay selection
screen when relay test option selected:
PRS-UM-DP-X-EN-Rev1.0-17.11.2021
1. Detector Settings
2. Relay Settings
3. Configuration
4. Test
5. Information
6. Reset
1. Display Test
2. Relay
Relay :1
Set
:
42