Panel program will display Line and Zone selection screen:
User should set the detector MODBUS address first. This address must be same with the
address assigned to detector.
Line No is the connected MODBUS channel that detector already connected. DPX Series
control panel has 2 MODBUS channels. They are marked as RS485-A which is Line No: 1 and
RS485-B which is line No: 2. If Line No is set to zero 0 detector will be disabled even it is
connected to panel.
Zone No is the logical segment that user want to assign this detector. If Zone No is set to
zero (0) detector will be disabled even it is connected to panel.

7.2.5 MODBUS Detector Alarm Settings:

DPX Series Gas Control Panel can able to read status and parameter information directly
from a Prosense Gas detector. To adjust alarm parameters user should select "1.Alarm
Settings" from "Detector Settings" menu
Panel program will display a generic window for user to set desired detector and alarm level
to set:
PRS-UM-DP-X-EN-Rev1.0-17.11.2021
Detector
: 001
Line No
: 1
Zone No
: 3
1. Alarm Settings
2. Calibration
3. Detector ON/OFF
4. Analog Detector
Detector
: 001
Alarm
: 1
Level
:
Auto-reset :
Relay
:
Off Delay
:
38