These settings should be same on detector side for correct recognition of detector status at
panel side. Any inconsistent settings might generate failure to recognize detector state
correctly. Once signal levels are adjusted the detector can be configured. To configure go
back to the previous menu via using back button.
7.2.4 MODBUS Detector Configuration:
DPX Series Gas Control Panel can read detector configuration details through MODBUS
communication from Prosense Gas Detectors. To start communication between detector
and panel detector must be set on through panel settings. User should set detector Modbus
address on detector side and set detector ON panel side while detector is connected and
working. To start select "Detector Settings" from main menu:
Then select "Detector ON/OFF" to setup a MODBUS detector
PRS-UM-DP-X-EN-Rev1.0-17.11.2021
Successful
1. Detector Settings
2. Relay Settings
3. Configuration
4. Test
5. Information
6. Reset
1. Alarm Settings
2. Calibration
3. Detector ON/OFF
4. Analog Detector
37