2 Technical Specifications

Power Source
Power Consumption
Inputs
Relay Outputs
Contacts rating
Display
LED indicators
Audible indicators
Audible Output
Network Output
MODBUS Output
Backup battery
Operating Temp.
Humidity
Housing
Weight
Main power fuse
Backup battery fuse
Warm-up time
Delay time
Special States
EMC conformity
IEC conformity
ATEX conformity
ATEX Label
Program Release
Special condition
Event log
Clock battery
PRS-UM-DP-X-EN-Rev1.0-17.11.2021
220VAC
27VDC/250mA - 6.75W max. (without connected detectors)
DPX4 : 4 x Analogue input
DPX8 : 8 x Analogue input
DPX32 : 2 x MODBUS input (16 + 16) + 8 x Analogue input
DPX64 : 2 x MODBUS input (32 + 32) + 8 x Analogue input
DPX128 : 2 x MODBUS input (64 + 64) + 8 x Analogue input
FAULT, ALARM1, ALARM2, ALARM3, OVERRANGE (optional programmable
relay)
3A, 24VDC
Graphic OLED (128x64)
FAULT, ALARM1, ALARM2, ALARM2, OVERRANGE status LEDs for each zone
(40 LEDs)
Power/On, FAULT, ALARM1, ALARM2, ALARM3, SYS-FAULT LEDs for overall
monitoring
Internal buzzer
Siren 24VDC/2A
Ethernet-RJ45 / MODBUS over Ethernet (optional)
RS485 MODBUS RTU Output for external device communication
2 x 12V 7A/h (Optional)
0
-10 : 60
C
15 - 95% non condensing
ABS IP66 (546 X 276 X 186 mm)
DPX4: 4kg
DPX8, DPX32, DPX64, DPX128: 6kg
2A
2A
Up to 2 minutes
Panel can recognize any special state in 2 minutes
Fault (Fault Relay is de-energised)
Alarm (Alarm Relays are energised)
Overrange (Overrange Relay is energised)
EN 61326-1 Group-1 Class-A
IEC 60079-29-1:2106
IEP 21 ATEX 0883X
[Ex Gb] IIC
V3.02.1.03
Do NOT install in hazardous area
Up to 500 records
RTC 3V/10mA
Table 2: Technical specifications