Range is measurement range of the detector. It can be defined as 0-100% LEL, 0-100%VOL,
0-10000PPM, 0-10000PPB.
Once all set press MENU button and panel will record the given values and show a
confirmation with "Successful" message.

7.2.2 Analogue Detector Alarm Settings:

Alarm levels for the analogue channel detectors must be defined at panel side. To set alarm
levels select "2. Alarm Settings" from Analog Detector menu. Panel program will display a
table to set each alarm:
The cursor on Channle number will be blinking. User must first set the number of channel
that wanted to set the alarm and than select which alarm level wanted to set via using up
and down buttons. When these parameters set and pressed the MENU button panle will
display default alarm paramaters:
User should adjust each parameters to desired value and press the MENU to shift next
paramater or digit.
PRS-UM-DP-X-EN-Rev1.0-17.11.2021
Channel
: 1
Alarm
: 1
Level
:
Auto-reset :
Direction
:
Hysteresis :
Channel
: 1
Alarm
: 1
Level
:
Auto-reset :
Direction
:
Hysteresis :
Channel
: 4
Alarm
: 1
Level
: 10%LEL
Auto-reset : YES
Direction
: Rising
Hysteresis : 03
35