7.3 Relay Settings:

DPX Series Control Panel has five relay outputs. Relay numbers and related events are
defined as below:
Relay No
Relay-1
Relay-2
Relay-3
Relay-4
Relay-5
These predefined events related relays cannot be altered. Only Relay-5 can be changed and
assigned to a different event. Also user can assign or remove zones from Relay-5. To change
relay settings select "2.Relay Settings" from main menu:
Relay parameters will be listed on display for user to select relay number to change. Program
will also guide user to update each parameter:
For relay number 2, 3 and 4 event type parameter cannot be changed as they are
permanently assigned to alarms. Relay-5 is assigned to overrange status and it can be
assigned to different event if needed.
Relays can be set to work in Energized or De-energized mode via adjusting "D. State"
parameter.
Off Delay is a time period as minute. It keeps relays active after the related event cleared by
given time period. If this feature is not necessary delay should be set to zero (00).
PRS-UM-DP-X-EN-Rev1.0-17.11.2021
Event
Monitoring area
FAULT
All Zones and Panel itself
ALARM-1
All Zones
ALARM-2
All Zones
ALARM-3
All Zones
OVERRANGE All Zones
Table 20: Relay assignments
1. Detector Settings
2. Relay Settings
3. Configuration
4. Test
5. Information
6. Reset
Relay No
:2
Event Type :ALRM1
D. State
: Energized
Off Delay
:00 Min
Zone from : 1
Zone to
: 8
Assignment
No alteration
No alteration
No alteration
No alteration
Can be altered